Trane CCAF manual Selection Procedures, Scroll Liquid Chiller - CGWF - Selection Example

Models: CCAF CGWF

1 40
Download 40 pages 21.88 Kb
Page 15
Image 15
Selection Procedures

Selection Procedures

The chiller capacity tables on the following pages cover the most frequently encountered leaving water temperatures. For temperature drops other than 10°F [5.6°C], refer to Table SP-1, Performance Adjustment Factors, shown below.

Additional chiller selections and performance information can be obtained through your local Trane sales office.

To select a Trane water-cooled scroll chiller, the following information is required:

1.Design load in tons of refrigeration

2.Design chilled water temperature drop

3.Design leaving chilled water temperature

4.Entering condenser water temperature

Evaporator flow rate (gpm) can be determined by using the following formula:

gpm =

Tons x 24

 

Chilled Water ￿T (F)

Condenser flow rate (gpm) can be determined by using the following formula:

gpm =

24 x (tons + (0.285 x compressor kW) Condenser Water ￿T (F)

Table SP-1. Performance adjustment factors

Fouling

Water

 

Evap.

 

Cond.

Factor

Delta T

Capacity

GPM

kW

GPM

 

8

0.997

1.231

1.000

0.997

0.00010

10

1.000

1.000

1.000

1.000

 

12

1.007

0.829

1.001

1.006

 

14

1.012

0.714

1.001

1.010

 

16

1.017

0.628

1.002

1.014

Note:

This selection procedure is for water only as the solution.

Scroll Liquid Chiller — (CGWF) — Selection Example:

Given:

System Load = 40 tons

Leaving Chilled Water Temperature (LCWT) = 44°F [6.7°C]

Entering Condenser Water Temperature (EWT) = 85°F [29.4°C]

Leaving Condenser Water Temperature (LWT) = 95°F [35°C]

Chilled Water Temperature Drop

=10°F [5.6°C]

1.From Table PD-1 (Performance Data), a CGWF 40 at the given conditions will produce 39.4 tons with a compressor power input of 30.3 kW and a unit EER of 15.6.

2.To determine the evaporator and condenser water pressure drops, the flow rates (gpm) must be determined. Using the formula above, this unit would require an evaporator flow rate of 95 gpm and a condenser flow rate of 115 gpm. (Compressor kW is found in the same table as the capacity.) The Evaporator Pressure Drop Curve, Chart PD-1, indicates that 95 gpm through a 40 ton evaporator results in a pressure drop of 13.8 feet of water. The Condenser Pressure Drop curve, Chart PD-2, indicates 115 gpm through a 40 ton condenser results in a pressure drop of 14 feet of water.

3.The final unit selection is:

Quantity (1) CGWF 40

Cooling Capacity = 39.4 tons

Entering/Leaving Chilled Water Temperatures = 54/44°F [12.2/6.7°C]

Chilled water flow rate = 95 gpm

Evaporator water pressure drop = 13.8 feet

Cooling water flow = 115 gpm

Condenser water pressure drop = 14 feet

Compressor power input = 30.3 kW

Unit EER = 15.6

Compressor Chiller – (CCAF) – Selection Example:

Select the unit for the following conditions:

A compressor chiller is required to produce 45 tons when matched with an air-cooled condenser. The leaving chilled water temperature is 44°F [6.7°C]. The evaporator temperature differential is 10°F [5.6°C]. The ambient temperature is 95°F [35°C].

1.Select the nominal unit size. The performance data is tabulated by leaving chilled water temperature. For example, the standard unit capacities at 44°F [6.7°C] leaving chilled water temperature are found on page 21. The system that best meets the tonnage requirement is a CCAF 50 matched with a CAUC C50. The unit capacity is 47.1 tons with a kW input of

56.3.The compressor chiller EER is

2.Calculate the required chilled water flow rate.

3. gpm =

Tons x 24

 

Chilled Water ￿T (F)

From this example,

gpm =

47.1 x 24 = 113

 

10

4.Determine the evaporator water pressure drop. The evaporator water pressure drop is located on page 22. Entering the evaporator chart at 113 gpm, the pressure drop for a CCAF 50 evaporator is 7.9 feet.

5.Unit Selection

The above procedure shows the proper selection for this example is a CCAF 50 with a CAUB C50 condenser operating as follows:

Capacity = 47.1

Entering/leaving chilled water temperature = 54/44°F [12.2/6.7°C]

Chilled water flow rate = 113 gpm

Evaporator water pressure drop = 7.9 feet

Compressor power input = 56.3

Unit EER = 10.0

CG-PRC012-EN

15

Page 15
Image 15
Trane CCAF manual Selection Procedures, Scroll Liquid Chiller - CGWF - Selection Example