Performance | Part Load |
Data | Performance |
|
|
|
|
Table PD-5. Part-load performance for CGWF 20-60 ton – 60 Hz in English units
Unit Size |
| 100% | IPLV |
| Tons | 19.9 |
|
20 | kW | 15.2 | 20.3 |
| EER | 15.5 |
|
| Tons | 24.5 |
|
25 | kW | 19.0 | 20.5 |
| EER | 15.4 |
|
| Tons | 29.2 |
|
30 | kW | 22.8 | 20.3 |
| EER | 15.3 |
|
| Tons | 39.4 |
|
40 | kW | 30.1 | 20.7 |
| EER | 15.6 |
|
| Tons | 48.6 |
|
50 | kW | 37.6 | 19.6 |
| EER | 15.4 |
|
| Tons | 59.4 |
|
60 | kW | 46.5 | 19.8 |
| EER | 15.2 |
|
Notes:
1.IPLV values are rated in accordance with ARI Standard
2.EER and IPLV values include compressor and control kW.
3.kW input is for compressors only.
Table
Unit Size |
| 100% | IPLV |
| Tons | 16.7 |
|
20 | kW | 12.4 | 21.0 |
| EER | 16.1 |
|
| Tons | 20.6 |
|
25 | kW | 15.5 | 20.9 |
| EER | 16.0 |
|
| Tons | 24.5 |
|
30 | kW | 18.5 | 20.7 |
| EER | 15.9 |
|
| Tons | 33.0 |
|
40 | kW | 24.5 | 21.3 |
| EER | 16.2 |
|
| Tons | 40.8 |
|
50 | kW | 30.6 | 20.3 |
| EER | 16.0 |
|
| Tons | 50.1 |
|
60 | kW | 37.6 | 20.4 |
| EER | 16.0 |
|
Notes:
1.IPLV values are rated in accordance with ARI Standard
2.EER and IPLV values include compressor and control kW.
3.kW input is for compressors only.
23 |