Trane CGWF Performance, Full Load, Data, Table PD-7. 60 Hz CCAF performance data in English units

Models: CCAF CGWF

1 40
Download 40 pages 21.88 Kb
Page 20
Image 20
Table PD-7. 60 Hz CCAF performance data in English units

Performance

Full Load

Data

Performance

 

 

 

 

Table PD-7. 60 Hz CCAF performance data in English units

Evaporator

 

 

 

 

 

 

Entering Condenser Air Temperature (F)

 

 

 

 

Leaving Water

Unit

Condenser

 

85

 

 

95

 

 

105

 

 

115

 

Temperature (F)

Size

Size

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

 

20

CAUC-C20

19.4

19.5

11.8

18.4

21.6

10.1

17.3

23.9

8.6

16.1

26.6

7.2

 

20

CAUC-C25

19.7

18.6

12.6

18.7

20.6

10.8

17.6

23.0

9.1

16.5

25.5

7.7

 

25

CAUC-C25

24.1

24.9

11.5

22.8

27.6

9.9

21.5

30.6

8.4

20.0

34.0

7.0

 

25

CAUC-C30

24.5

23.4

12.5

23.3

26.0

10.7

22.0

28.9

9.1

20.6

32.1

7.7

42

30

CAUC-C30

28.8

29.1

11.8

27.3

32.2

10.1

25.7

35.7

8.6

24.1

39.6

7.3

 

30

CAUC-C40

29.2

27.0

12.9

27.8

29.9

11.1

26.3

33.2

9.5

24.7

36.9

8.0

 

40

CAUC-C40

38.7

38.8

11.9

36.7

43.0

10.2

34.5

47.8

8.6

32.2

53.2

7.2

 

40

CAUC-C50

39.1

37.4

12.5

37.1

41.6

10.6

35.0

46.2

9.0

32.7

51.4

7.6

 

50

CAUC-C50

47.6

50.2

11.3

45.1

55.6

9.7

42.5

61.8

8.2

39.7

68.4

6.9

 

50

CAUC-C60

48.4

47.0

12.3

46.0

52.2

10.5

43.5

58.2

8.9

40.8

64.6

7.6

 

60

CAUC-C60

56.9

58.4

11.6

54.0

64.8

10.0

50.9

71.8

8.5

47.6

79.8

7.1

 

60

CAUC-C80

57.5

53.6

12.8

54.7

59.6

11.0

51.8

66.4

9.3

48.6

73.8

7.9

 

20

CAUC-C20

20.0

19.7

12.1

19.0

21.8

10.4

17.8

24.2

8.8

16.6

26.8

7.4

 

20

CAUC-C25

20.4

18.8

12.9

19.3

20.8

11.0

18.2

23.2

9.3

17.1

25.7

7.9

 

25

CAUC-C25

24.9

25.1

11.8

23.6

27.9

10.1

22.2

30.9

8.6

20.7

34.3

7.2

 

25

CAUC-C30

25.3

23.7

12.7

24.1

26.3

10.9

22.7

29.2

9.3

21.3

32.4

7.9

44

30

CAUC-C30

29.7

29.4

12.1

28.2

32.6

10.3

26.6

36.1

8.8

24.9

40.0

7.4

 

30

CAUC-C40

30.2

27.2

13.2

28.8

30.2

11.4

27.2

33.5

9.7

25.6

37.2

8.2

 

40

CAUC-C40

39.9

39.2

12.1

37.8

43.4

10.4

35.6

48.2

8.8

33.3

53.6

7.4

 

40

CAUC-C50

40.3

37.8

12.7

38.3

42.0

10.9

36.1

46.6

9.2

33.8

51.8

7.8

 

50

CAUC-C50

49.1

50.6

11.6

46.6

56.2

9.9

43.9

62.2

8.4

41.0

69.0

7.1

 

50

CAUC-C60

50.0

47.4

12.6

47.5

52.6

10.8

44.9

58.6

9.2

42.2

65.2

7.7

 

60

CAUC-C60

58.7

58.5

12.0

55.7

65.4

10.2

52.6

72.6

8.7

49.2

80.6

7.3

 

60

CAUC-C80

59.3

54.0

13.1

56.5

60.0

11.3

53.5

66.8

9.6

50.3

74.4

8.1

 

20

CAUC-C20

20.7

19.9

12.4

19.6

22.0

10.6

18.4

24.4

9.0

17.2

27.1

7.6

 

20

CAUC-C25

21.0

18.9

13.2

20.0

21.0

11.3

18.8

23.4

9.6

17.6

25.9

8.1

 

25

CAUC-C25

25.7

25.4

12.1

24.3

28.2

10.3

22.9

31.2

8.8

21.4

34.6

7.4

 

25

CAUC-C30

26.2

23.9

13.1

24.9

26.5

11.2

23.5

29.5

9.5

22.0

32.6

8.1

46

30

CAUC-C30

30.7

29.7

12.3

29.1

32.9

10.6

27.5

36.4

9.0

25.7

40.4

7.6

 

30

CAUC-C40

31.2

27.4

13.6

29.7

30.4

11.7

28.2

33.8

10.0

26.5

37.5

8.4

 

40

CAUC-C40

41.1

38.6

12.7

39.0

43.8

10.6

36.8

48.8

9.0

34.4

54.0

7.6

 

40

CAUC-C50

41.6

38.0

13.1

39.5

42.2

11.2

37.3

47.0

9.5

35.0

52.2

8.0

 

50

CAUC-C50

50.6

51.2

11.8

48.0

56.6

10.1

45.3

62.8

8.6

42.3

69.8

7.2

 

50

CAUC-C60

51.6

47.8

12.9

49.1

53.2

11.0

46.4

59.0

9.4

43.6

65.6

7.9

 

60

CAUC-C60

60.5

59.4

12.2

57.5

66.0

10.4

54.3

73.2

8.9

50.9

81.2

7.5

 

60

CAUC-C80

61.2

54.4

13.4

58.3

60.6

11.5

55.2

67.4

9.8

52.0

75.0

8.3

Notes:

1.Ratings based on sea level altitude and evaporator fouling factor of 0.00010.

2.Consult Trane representative for performance at temperatures outside of the ranges shown.

3.kW input is for compressors only.

4.EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors and control power.

5.Ratings are based on an evaporator temperature drop of 10°F.

6.Interpolation between points is permissible. Extrapolation is not permitted.

7.Rated in accordance with ARI Standard 550/590-98.

20

CG-PRC012-EN

Page 20
Image 20
Trane CGWF manual Performance, Full Load, Data, Table PD-7. 60 Hz CCAF performance data in English units