Trane Performance, Full Load, Data, Table PD-8. 60 Hz CCAF performance data in English units

Models: CCAF CGWF

1 40
Download 40 pages 21.88 Kb
Page 21
Image 21
Table PD-8. 60 Hz CCAF performance data in English units

Performance

Full Load

Data

Performance

 

 

 

 

Table PD-8. 60 Hz CCAF performance data in English units

Evaporator

 

 

 

 

 

 

Entering Condenser Air Temperature (F)

 

 

 

 

Leaving Water

Unit

Condenser

 

85

 

 

95

 

 

105

 

 

115

 

Temperature (F)

Size

Size

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

Tons

kW

EER

 

20

CAUC-C20

21.3

20.1

12.6

20.2

22.2

10.8

19.0

24.6

9.2

17.7

27.3

7.7

 

20

CAUC-C25

21.7

19.1

13.5

20.6

21.2

11.6

19.4

23.6

9.8

18.2

26.2

8.3

 

25

CAUC-C25

26.5

25.7

12.3

25.1

28.4

10.5

23.7

31.5

9.0

22.1

34.9

7.6

 

25

CAUC-C30

27.0

24.1

13.4

25.7

26.7

11.5

24.3

29.6

9.8

22.8

32.9

8.3

48

30

CAUC-C30

31.6

30.0

12.6

30.1

33.2

10.8

28.4

36.8

9.2

26.6

40.7

7.8

 

30

CAUC-C40

32.2

27.7

13.9

30.7

30.7

11.9

29.1

34.1

10.2

27.4

37.8

8.7

 

40

CAUC-C40

42.4

40.0

12.6

40.2

44.4

10.8

37.9

49.2

9.2

35.5

54.6

7.8

 

40

CAUC-C50

42.8

38.4

13.3

40.7

42.6

11.4

38.5

47.4

9.7

36.1

52.6

8.2

 

50

CAUC-C50

52.2

51.6

12.1

49.5

57.2

10.3

46.7

63.4

8.8

43.7

70.2

7.4

 

50

CAUC-C60

53.2

48.2

13.2

50.6

53.6

11.3

47.9

59.6

9.6

45.0

66.2

8.1

 

60

CAUC-C60

62.4

60.2

12.4

59.3

66.6

10.6

56.0

74.0

9.1

52.5

82.0

7.7

 

60

CAUC-C80

63.1

54.8

13.8

60.2

61.8

11.8

57.0

67.8

10.1

53.7

75.4

8.5

 

20

CAUC-C20

21.9

20.3

12.8

20.8

22.5

11.0

19.6

24.9

9.4

18.3

27.6

7.9

 

20

CAUC-C25

22.3

19.3

13.8

21.2

21.4

11.8

20.1

23.8

10.1

18.8

26.4

8.5

 

25

CAUC-C25

27.3

25.9

12.6

25.9

28.7

10.8

24.4

31.8

9.2

22.9

35.2

7.8

 

25

CAUC-C30

27.9

24.3

13.7

26.5

26.9

11.8

25.1

29.9

10.0

23.5

33.1

8.5

50

30

CAUC-C30

32.6

30.3

12.8

31.0

33.6

11.0

29.3

37.2

9.4

27.5

41.1

8.0

 

30

CAUC-C40

33.2

27.9

14.2

31.7

30.9

12.2

30.0

34.3

10.4

28.3

38.1

8.9

 

40

CAUC-C40

43.6

40.4

12.9

41.4

44.8

11.0

39.1

49.6

9.4

36.6

55.0

8.0

 

40

CAUC-C50

44.1

38.8

13.6

42.0

43.0

11.7

39.7

47.8

9.9

37.2

53.0

8.4

 

50

CAUC-C50

53.7

52.2

12.3

51.0

57.8

10.5

48.1

64.0

9.0

45.1

71.0

7.6

 

50

CAUC-C60

54.8

48.6

13.5

52.2

54.0

11.5

49.4

60.0

9.8

46.4

66.6

8.3

 

60

CAUC-C60

64.3

60.8

12.6

61.1

67.4

10.8

57.8

74.6

9.3

54.2

82.8

7.8

 

60

CAUC-C80

65.1

55.4

14.0

62.1

61.4

12.1

58.8

68.4

10.3

55.4

76.0

8.7

Notes:

1.Ratings based on sea level altitude and evaporator fouling factor of 0.00010.

2.Consult Trane representative for performance at temperatures outside of the ranges shown.

3.kW input is for compressors only.

4.EER = Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors and control power.

5.Ratings are based on an evaporator temperature drop of 10°F.

6.Interpolation between points is permissible. Extrapolation is not permitted.

7.Rated in accordance with ARI Standard 550/590-98.

CG-PRC012-EN

21

Page 21
Image 21
Trane CGWF manual Performance, Full Load, Data, Table PD-8. 60 Hz CCAF performance data in English units