Trane CGWF manual CCAF 40-60 Ton, Dimensional, Data

Models: CCAF CGWF

1 40
Download 40 pages 21.88 Kb
Page 36
Image 36
CCAF 40-60 Ton

Dimensional

 

Data

CCAF 40-60 Ton

 

 

 

 

English Dimensions

 

 

 

Unit Size

A

B

C

D

E

F

 

40 Ton

5’-1 3/4”

1’-3 3/4”

1’-11 1/4”

2 1/2”

3’-5”

1’-4 1/4”

50 Ton

5’-1 1/2”

1’-3 1/2”

2’-1 1/8”

3”

3’-10”

1’-6 1/8”

60 Ton

5’-1 1/2”

1’-3 1/2”

2’-0 7/8”

3”

3’-10”

1’-6 1/8”

 

 

 

 

 

 

 

 

 

 

 

 

Metric Dimensions (mm)

 

 

 

Unit Size

A

B

C

D

E

F

 

40 Ton

1568

400

591

64

1041

413

50 Ton

1562

394

638

76

1168

480

60 Ton

1562

394

632

76

1168

460

Notes:

1.Dimensions in ( ) are in millimeters.

2.Add 3/4” (19 mm) for units with insulation.

3.Dimensional tolerance ± 1/4” (6.4).

4.Tube installation at either end of evaporator.

36

CG-PRC012-EN

Page 36
Image 36
Trane CGWF manual CCAF 40-60 Ton, Dimensional, Data