Performance | Full Load |
Data | Performance |
|
|
|
|
Table PD-2. 60 Hz CGWF performance data in Metric units
Evaporator |
|
|
| Entering Condenser Water Temperature (C) |
|
| ||||
Leaving Water | Unit |
| 25 |
|
| 30 |
|
| 35 |
|
Temperature (C) | Size | kWo | kWi | COP | kWo | kWi | COP | kWo | kWi | COP |
| 20 | 70.4 | 14.2 | 5.0 | 67.7 | 15.5 | 4.4 | 64.7 | 17.1 | 3.8 |
| 25 | 87.1 | 17.7 | 4.9 | 83.5 | 19.4 | 4.3 | 79.8 | 21.8 | 3.7 |
6 | 30 | 104.0 | 21.2 | 4.9 | 99.6 | 23.2 | 4.3 | 95.1 | 25.6 | 3.7 |
| 40 | 139.5 | 28.0 | 5.0 | 133.9 | 30.7 | 4.4 | 128.1 | 33.8 | 3.8 |
| 50 | 172.4 | 35.0 | 4.9 | 165.3 | 38.3 | 4.3 | 157.9 | 42.2 | 3.7 |
| 60 | 211.0 | 43.2 | 4.9 | 202.2 | 47.3 | 4.3 | 193.1 | 52.0 | 3.7 |
| 20 | 75.7 | 14.3 | 5.3 | 72.7 | 15.7 | 4.6 | 69.6 | 17.3 | 4.0 |
| 25 | 93.5 | 17.8 | 5.3 | 89.8 | 19.5 | 4.6 | 85.8 | 21.5 | 4.0 |
8 | 30 | 111.4 | 21.4 | 5.2 | 106.8 | 23.4 | 4.6 | 102.0 | 25.7 | 4.0 |
| 40 | 150.3 | 28.2 | 5.3 | 144.5 | 30.9 | 4.7 | 138.3 | 34.1 | 4.1 |
| 50 | 185.3 | 35.2 | 5.3 | 177.7 | 38.6 | 4.6 | 169.9 | 42.5 | 4.0 |
| 60 | 226.0 | 43.5 | 5.2 | 216.8 | 47.6 | 4.6 | 207.2 | 52.4 | 4.0 |
| 20 | 80.8 | 14.4 | 5.6 | 77.7 | 15.8 | 21.7 | 74.4 | 17.4 | 4.3 |
| 25 | 99.9 | 17.9 | 5.6 | 95.9 | 19.6 | 21.5 | 91.8 | 21.6 | 4.8 |
10 | 30 | 119.0 | 21.5 | 5.5 | 114.1 | 23.6 | 21.4 | 109.1 | 25.9 | 4.2 |
| 40 | 159.9 | 28.4 | 5.6 | 153.8 | 31.2 | 21.8 | 147.3 | 34.3 | 4.3 |
| 50 | 197.9 | 35.5 | 5.6 | 185.9 | 35.2 | 23.3 | 181.7 | 42.8 | 4.2 |
| 60 | 240.7 | 43.8 | 5.5 | 231.0 | 48.0 | 21.2 | 221.0 | 52.8 | 4.2 |
Notes:
1.Rated in accordance with ARI Standard
2.Consult Trane representative for performance at temperatures outside of the ranges shown.
3.kWi input is for compressors only.
4.COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.
5.Ratings are based on an evaporator temperature drop of 5.6°C.
6.Interpolation between points is permissible. Extrapolation is not permitted.
17 |