Trane CCAF Performance, Full Load, Data, Table PD-4. 50 Hz CGWF performance data in Metric units

Models: CCAF CGWF

1 40
Download 40 pages 21.88 Kb
Page 19
Image 19
Table PD-4. 50 Hz CGWF performance data in Metric units

Performance

Full Load

Data

Performance

 

 

 

 

Table PD-4. 50 Hz CGWF performance data in Metric units

Evaporator

 

 

 

Entering Condenser Water Temperature (C)

 

 

Leaving Water

Unit

 

25

 

 

30

 

 

35

 

Temperature (C)

Size

kWo

kWi

COP

kWo

kWi

COP

kWo

kWi

COP

 

20

70.4

14.2

5.0

67.7

15.5

4.4

64.7

17.1

3.8

 

20

59.4

11.4

5.2

57.0

12.6

4.5

54.5

14.0

3.9

 

25

73.4

14.2

5.2

70.5

15.7

4.5

67.5

17.3

3.9

6

30

87.3

17.0

5.1

83.9

18.7

4.5

80.3

20.7

3.9

 

40

117.6

22.4

5.2

112.9

24.8

4.6

108.0

27.5

3.9

 

50

145.3

28.0

5.2

139.7

30.9

4.5

133.7

34.2

3.9

 

60

178.4

34.5

5.2

171.7

38.0

4.5

164.0

41.9

3.9

 

20

63.7

11.4

5.6

61.2

12.6

4.9

58.5

14.0

4.2

 

25

78.6

14.3

5.5

75.6

15.7

4.8

72.3

17.4

4.2

8

30

93.5

17.1

5.5

89.9

18.8

4.8

86.1

20.8

4.1

 

40

126.0

22.5

5.6

121.0

24.8

4.9

115.8

27.8

4.2

 

50

155.6

28.2

5.5

149.5

31.0

4.8

143.2

34.3

4.2

 

60

190.4

34.7

5.5

183.3

38.2

4.8

175.6

42.2

4.2

 

20

68.1

11.4

6.0

65.4

12.6

5.2

62.7

14.0

4.5

 

25

84.0

14.3

5.9

80.8

15.8

5.1

77.4

17.5

4.4

10

30

99.9

17.2

5.8

96.2

18.9

5.1

92.2

20.9

4.4

 

40

134.8

22.6

6.0

129.5

24.9

5.2

124.2

27.7

4.5

 

50

166.4

28.3

5.9

160.1

31.1

5.1

153.4

34.5

4.4

 

60

203.0

34.9

5.8

195.3

38.4

5.1

187.2

42.4

4.4

Notes:

1.Rated in accordance with ARI Standard 550/590-98 with fouling factors of 0.0176 in the evaporator and 0.044 in the condenser.

2.Consult Trane representative for performance at temperatures outside of the ranges shown.

3.kWi input is for compressors only.

4.COP = Coefficient of Performance (kWo/total kW). Total kW include compressors and control power.

5.Ratings are based on an evaporator and condenser temperature drop of 5.6°C.

6.Interpolation between points is permissible. Extrapolation is not permitted.

CG-PRC012-EN

19

Page 19
Image 19
Trane CCAF manual Performance, Full Load, Data, Table PD-4. 50 Hz CGWF performance data in Metric units