Features and Benefits

Features and Benefits

Standard CVGF Features

The following features are provided as standard with allTrane Model CVGF chillers:

Hermetic two-stage centrifugal compressor-motor assembly with integral lubrication system and economizer cycle

Evaporator and condenser assembly

Prewired instrument and control panel

Oil charge

Integral oil heaters

Isolation pads

Wiring and oil system interconnection to main control panel

Advance motor protection

•Two-stage gear drive with economized cycle for high efficiency and high reliability

Liquid cooled hermetic induction motor; the motor operates at lower temperatures for longer motor life

Optional Features

Unit and remote wye-delta mounted starters

Unit mounted, floor mounted, and wall mounted solid state starters.

Across-the-line, Primary Reactor, and AutoTransformer Remote mounted starter for medium/high voltage

Marine waterboxes for evaporator and condenser

Factory-applied thermal insulation

One-inch deflection spring isolators for vibration-sensitive installations

Refrigerant available from a local distributor

Building automation systems (BAS) Interface

Factory testing

Applications

Comfort cooling

Industrial process cooling

Patents

Polygon drive for refrigeration compressor impellers

Centrifugal compressor sump demister

Internal oil filter

Thermosiphonic oil cooler

Compressor height and alignment adjustment

Oil return using hot gas for motive force

Centrifugal impeller assembly

Internal oil filter

Orifice System

Simplified orifice system with improved part load performance down to 20 percent part load

Advanced Heat Transfer Surfaces

Evaporator and condenser tubes use the latest heat transfer surfaces

Less refrigerant needed due to advanced patented evaporator design

Compact Size

Designed with the retrofit and replacement market in mind

The 400 to 500 NTON sizes can fit through most double-width doors

Small footprint of the CVGF chiller saves valuable equipment room space

Simple Installation

Simplified piping; the only water piping required is for the evaporator and condenser

Simple power connection

Unit mounted starter eliminates additional jobsite labor requirements

Environmental Features and Benefits

Improved Efficiency:

High Efficiency: 0.55 kW/Ton at ARI conditions

Motor cooling vented to economizer cycle, efficiency advantage

HFC-134 optimized inlet guide vanes and impellers for improved cycle efficiency using computational fluid dynamics

Reduced Emissions:

Over 30 percent joint reduction in compressor/motor assembly compared to previous designs

Patented integral heaters imbedded into the compressor casting, no seals no leaks

Beaded flat gasket technology instead of O-rings, lower susceptibility to developing leaks

Minimal NPT pipe threads on chiller system, SAE O-ring boss fitting, lower leak potential

Oil sump internal to compressor/ motor assembly with internal pump/ motor; eliminates vent and drain lines, leak prevention

Patented internal oil filter prevents leaks and contamination from pipes; filter is isolated and easily replaced

Advanced evaporator design minimizes the refrigerant charge; a reduced charge reduces the exposure to the environment in the event of a catastrophic charge loss

Additional Features and Benefits

Patented polygon attachment instead of a keyed shaft, self-balancing

Easy to replace motor terminals

Motor/stator assembly is easily removed; speed assembly can be removed independent of the high- speed assembly

Rolling element bearings

Hydrodynamic bearings

Advanced evaporator design: no eliminator necessary with an advanced suction baffle design

All metric fasteners