![Momentary Power Loss and](/images/new-backgrounds/54983/5498333x1.webp)
Standard
Controls Protections
Momentary Power Loss and
Distribution Fault Protection
An MPL has occurred when the motor no longer consumes power. An MPL may be caused by any drop or sag in the voltage that results in a change in the direction of power flow. Different operating conditions, motor loads, motor size, inlet guide vane (IGV) position, etc. may result in different levels at which this may occur. It is difficult to define an exact voltage sag or voltage level at which a particular motor will no longer consume power, but we are able to make some general statements concerning MPL protection:
The chiller will remain running under the following conditions:
•
•
•
•
The chiller may shut down under the following conditions:
•
•
•
Current Overload Protection
The control panel will monitor the current drawn by each line of the motor and shut the chiller off when the highest of the three line currents exceeds the trip curve. A manual reset diagnostic describing the failure will be displayed. The current overload protection does not prohibit the chiller from reaching its
The chiller protects itself from damage due to current overload during starting and running modes, but is allowed to reach
High Motor-Winding Temperature Protection
This function monitors the motor temperature and terminates chiller operation when the temperature is excessive. The controller monitors each of the three
Surge Detection Protection
Surge detection is based on current fluctuations in one of three phases. The default detection criterion is two occurrences of RMS current change of 30 percent within 0.8 seconds in 60 + 10 percent seconds. With theTracer chiller controller, the detection criterion is adjustable.
Overvoltage and Undervoltage Protection
The unit will be shut down with an automatic reset if the line voltage is below or above 10 percent of nominal.
Must trip = 15 percent of nominal.
Time to trip = minimum of 1 minute, 10 seconds and maximum of 5 minutes, 20 seconds. Overvoltage and undervoltage protection can be disabled using TechView.
Power Factor and kW Measurement
A’Restart Inhibit
When the start is inhibited by the
1 7 |