Installation
Waterside Economizer
Start-up Sequence
1Set the thermostat to the highest position.
2Set the thermostat system switch to COOL with the fan control to AUTO. The compressor should NOT run.
3Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/temperature plugs and comparing to tables contained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately
4Check the cooling refrigerant pressures against values in Table 7 on page 75. NOTE: If cooling mode is activated, and the entering water temperature of the heat pump falls below 55ºF, the
5Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de- energize.
6Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7Turn the thermostat to the lowest setting.
8Set the thermostat system switch to the HEAT position.
9Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately
10Check the heating refrigerant pressures against values in Table 7 on page 75. NOTE: For units with boilerless electric heat option...In heating mode, if the entering water temperature of the heat pump falls below 45ºF, the electric heater will be energized, and compressor operation will halt. Once the entering water temperature rises above 50ºF, the boil- erless controls returns the unit to normal operation.
11Set the thermostat to maintain the desired space temperature.
12Instruct the owner on system operation.
6 4 |