Installation
Supply-Air Ductwork
Install the 1" (25.4 mm)
•Model GEH 1/2 to 5 ton = in a box on the side of the unit
•Model GEV 1/2 to 10ton = inside of the refrigeration section of the unit
•Model GEH 6 to 15 ton = of the re- frigeration section of the unit
•Model GEV 12 1/2 to 25 ton = facto- ry ship with a duct collar installed for units containing a top supply- air location. For units with a back or front
When attaching the field ductwork to the unit, provide a watertight flexible connector at the unit to prevent oper- ating sounds from transmitting through the ductwork. See Figure 4.
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
Return-Air Ductwork
Install the 1"/2" (25.4/50.8 mm) adjust- able filter rack to the horizontal equip- ment only with the use of (4) 5/16"
(7.94 mm) factory supplied Torx head screws. The vertical equipment factory ships with the filter rack and filter(s) in- stalled.
When attaching the field ductwork to the unit, provide a water tight flexible connector at the unit to prevent oper- ating sounds from transmitting through the ductwork. See Figure 5.
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
Figure 4: Flexible
Figure 5: Flexible