Trane Modu manual Electric Heat Installation, Electric Heat Coil Wiring Procedure

Models: Modu SCWG 020, SCWG 025, SCWG 030, SCWG 035, SIWG 020, SIWG 025, SIWG 030, SIWG 035, SCRG 020, SCRG 025, SCRG 032, SIRG 020, SIRG 025, SIRG 032 SCWG 020, SCWG 025, SCWG 030, SCWG 035, SWG 020, SWG 025, SWG 030, SWG 035, SCRG 020, SCRG 025, SCRG 032, SRG 020, SCRG 025, SCRG 032

1 124
Download 124 pages 57.08 Kb
Page 46
Image 46

Pre-Startup

Installation Requirements

Electric Heat Installation

The electric heat option consists of a single stage heater and is used in IntelliPak units or units with a field- installed thermostat. The electric heater ships separate for field installation and wiring. Available heater kW per unit size is listed inTable I-PR-3. Electric heat can be installed on units with either a vertical or horizontal discharge. However, it cannot be installed on units with plenums. See Figure I-PR-10, Tables I-PR-4, and I-PR-5 for electric heat dimensional data.

Table I-PR-3. Available Electric Heat kW

Unit Size

Heater kW

20Tons

16

25Tons

20

30Tons

24

32Tons

26

35Tons

28

Installation Procedure

1.Remove the fan discharge shipping covers, if they have not already been removed.

2.Install the open-cell gasket around the discharge opening on the heater.

3.Position the electric heater so that the unit fan discharge openings line up with the electric heater openings. For a vertical discharge unit, position the electric heater as shown in Figure I-PR- 10.

4.Use the hole pattern in the electric heat as a template for marking and drilling 3/16” diameter holes in the unit.

5.Bolt the electric heaters to the unit using 1/4” sheetmetal screws.

Note: It is very important that electric heaters are selected based on unit voltage and tonnage because discharge opening sizes vary by unit tonnage.

Electric Heat Coil Wiring Procedure

1.Before wiring the electric heater, remove the unit wiring diagram from the unit control panel and refer to the connection points.

!WARNING

Disconnect electrical power source before wiring electric heat to unit to prevent risk of injury or death from electrical shock.

2.Punch out the appropriate knockouts in the electric heater control box and on the unit’s left side panel. Run the wires down the side of the unit from the heater to the lower unit control box. Place the wire in conduit in accordance with local code.

!CAUTION

Use only copper conductors for electrical connections to prevent equipment damage.

Figure I-PR-10. Vertical discharge electric heat installation.

Figure I-PR-11. Electric heater dimensions.

Table I-PR-4. Electric Heat Dimensions - English - (inches)

Unit Size

B1

B2

Z

20Tons

10 3/4

15 5/8

27 3/4

25Tons

12 1/4

15 5/8

26 3/4

30, 32, 35Tons

14 3/4

15 5/8

23 3/4

Table I-PR-5. Electric Heat Dimensions - Metric - (mm)

Unit Size

B1

B2

Z

20Tons

273

397

705

25Tons

311

397

679

30, 32, 35Tons

375

397

603

46

SCXG-SVX01B-EN

Page 46
Image 46
Trane Modu manual Electric Heat Installation, Electric Heat Coil Wiring Procedure, Table I-PR-3. Available Electric Heat kW