Trane Programmable Night Setback Zone Sensors, ConstantVolume Zone Sensor BAYSENS019 Description

Models: Modu SCWG 020, SCWG 025, SCWG 030, SCWG 035, SIWG 020, SIWG 025, SIWG 030, SIWG 035, SCRG 020, SCRG 025, SCRG 032, SIRG 020, SIRG 025, SIRG 032 SCWG 020, SCWG 025, SCWG 030, SCWG 035, SWG 020, SWG 025, SWG 030, SWG 035, SCRG 020, SCRG 025, SCRG 032, SRG 020, SCRG 025, SCRG 032

1 124
Download 124 pages 57.08 Kb
Page 55
Image 55

Pre-Startup

Installation Requirements

Programmable Night Setback Zone Sensors

Programmable night setback (NSB) zone sensors provide programming and zone temperature sensing for the self- contained unit. It allows the user to monitor room temperatures and program settings in the space, without having to access the unit control panel.

Reference programming instructions for these zone sensors on page 64.

ConstantVolume Zone Sensor

BAYSENS019 Description

This seven day programmable sensor with night setback has four periods for occupied\unoccupied programming per day. If power is interrupted, the program retains in permanent memory. If power is off longer than 2 hours, only the clock and day may have to be reset.

The six programming keys on the front of the zone sensor allow selection of system modes (heat, cool, auto, and off), two fan modes (on and auto). The zone sensor has dual temperature selection with programmable start time capability.

The occupied cooling setpoint ranges between 40 and 80 F.The warmup setpoint ranges are between 50 and 90 F with a 2 degree deadband. The unoccupied cooling setpoint ranges between 45 and 98 F.The heating setpoint ranges between 43 and 96 F.

Two liquid crystal displays (LCD) display zone temperature, setpoints, week day, time, and operational mode symbols.

The DIP switches on the subbase enable or disable applicable functions; i.e. morning warmup, economizer minimum CFM override during unoccupied status, Fahrenheit or Centigrade, supply air tempering, remote zone temperature sensor, 12/24 hour time display, smart fan, and computed recovery.

During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts activates.

Variable Air Volume Zone Sensor

BAYSENS020B Description

This seven day programmable sensor with night setback has four periods for occupied\unoccupied programming per day. Either one or all four periods can be programmed. If power is interrupted, the program retains in permanent memory. If power is off longer than 2 hours, only the clock and day may have to be reset.

The zone sensor keypad allows you to select occupied/unoccupied periods with two temperature inputs (cooling supply air temperature and heating warmup temperature) per occupied period. The occupied cooling setpoint ranges be- tween 40 and 80 F.The warmup setpoint ranges between 50 and 90 F with a 2 degree deadband. The unoccupied cooling setpoint ranges between 45 and 98 F.The heating setpoint ranges be- tween 43 and 96 F.

The liquid crystal display (LCD) displays zone temperature, setpoints, week day, time, and operational mode symbols.

The DIP switches on the subbase enable or disable applicable functions; i.e. morning warmup, economizer minimum position override during unoccupied status, heat installed, remote zone temperature sensor, 12/24 hour time display, and daytime warmup. During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of single pole double throw contacts activates.

Figure I-PR-24. BAYSENS019, Programmable

Figure I-PR-25. BAYSENS020, Programmable

night setback sensor, Accessory Model

Number Digit 6 = G

night-setback sensor,

 

Accessory Model Number Digit 6 = J

SCXG-SVX01B-EN

55

Page 55
Image 55
Trane Modu manual Programmable Night Setback Zone Sensors, ConstantVolume Zone Sensor BAYSENS019 Description