Trane SS-PRC003-EN manual Performance, DataSystem, AmbientTemperature F

Models: SS-PRC003-EN

1 79
Download 79 pages 17.04 Kb
Page 18
Image 18
Manual background

Performance

DataSystem

Table PD-5 — Gross Cooling Capacities (MBh) TTA100A Condensing Unit withTWE100A Air Handler

 

 

 

 

 

(I-P)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

 

95

 

 

 

 

 

105

 

 

 

 

 

115

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°F)

 

 

 

 

 

 

 

 

 

 

 

CFM

Bulb

 

 

61

67

73

 

61

 

67

 

73

 

61

67

73

 

61

 

67

73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

 

TGC

SHC TGC SHC TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

 

TGC SHC TGC SHC TGC SHC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

104.7

81.7

115.8

68.5

127.7

46.8

 

100.9

79.7

111.5

66.8

 

123.0

45.1

96.8

77.7

107.1

65.0

118.1

43.5

 

92.4

75.5

102.5

63.2

112.9

41.7

3025

80

105.2

95.0

116.1

78.6

127.8

61.1

 

101.5

93.1

111.9

76.8

 

123.2

59.3

97.5

91.1

107.5

75.0

118.3

57.5

 

93.3

89.0

102.9

73.0

113.3

55.6

 

85

106.9

106.9

116.3

92.0

128.1

74.9

 

103.8

103.8

112.1

90.1

 

123.5

73.1

100.4

100.4

107.7

88.1

118.7

71.3

 

96.9

96.9

103.1

86.1

113.7

69.5

 

90

112.3

112.3

116.8

105.4

128.4

88.7

 

109.1

109.1

112.7

103.5

123.8

86.9

105.7

105.7

108.4

101.6 119.0

85.1

 

102.1 102.1 104.1

99.7

113.8

82.9

 

75

106.8

85.3

118.0

67.1

129.8

47.6

 

102.8

83.3

113.6

65.3

 

124.9

46.0

98.6

81.2

109.0

63.4

119.8

44.2

 

94.2

79.1

104.3

61.5

114.5

42.4

3350

80

107.5

99.9

118.3

82.1

130.0

63.0

 

103.7

98.0

113.9

80.3

 

125.2

61.2

99.6

96.0

109.4

78.4

120.2

59.4

 

95.4

93.9

104.5

76.0

115.0

57.5

 

85

110.4

110.4

118.4

96.5

130.3

78.1

 

107.1

107.1

114.1

94.6

 

125.5

76.3

103.7

103.7

109.6

92.6

120.6

74.5

 

100.0 100.0 104.9

90.5

115.4

72.6

 

90

116.1

116.1

119.2

111.2

130.5

93.1

 

112.7

112.7

115.0

109.3

125.6

90.9

109.1

109.1

110.7

107.4 120.7

89.0

 

105.4 105.4 106.3

105.4 115.6

87.0

 

75

108.6

88.8

119.7

69.3

131.5

48.5

 

104.5

86.8

115.2

67.4

 

126.5

46.8

100.2

84.7

110.6

65.5

121.2

44.9

 

95.6

82.4

105.7

63.5

115.8

43.0

3675

80

109.5

104.7

120.1

85.4

131.7

64.8

 

105.6

102.7

115.4

83.2

 

126.8

63.1

101.6

100.7

110.8

81.2

121.7

61.2

 

97.0

97.0

105.9

79.1

116.4

59.3

 

85

113.5

113.5

120.3

100.8

132.1

81.1

 

110.1

110.1

115.8

98.8

 

127.2

79.3

106.4

106.4

111.2

96.8

122.1

77.5

 

102.6 102.6 106.5

94.8

116.8

75.6

 

90

119.4

119.4

121.4

116.8

132.2

96.8

 

115.8

115.8

117.2

114.9

127.3

94.9

112.1

112.1

112.2

112.2 122.3

92.9

 

108.2 108.2 108.3

108.3 117.0

90.9

 

75

110.1

92.1

121.2

71.3

132.9

49.2

 

105.9

90.0

116.6

69.4

 

127.8

47.4

101.5

87.9

111.9

67.5

122.4

45.5

 

96.9

85.7

106.9

65.6

116.8

43.6

4000

80

111.4

109.2

121.4

88.2

133.2

66.6

 

107.5

107.3

116.9

86.2

 

128.2

64.8

103.1

103.1

112.1

84.2

123.0

63.0

 

99.3

99.3

107.2

82.0

117.6

61.1

 

85

116.3

116.3

121.9

105.0

133.6

84.0

 

112.7

112.7

117.4

103.0

128.6

82.2

108.9

108.9

112.7

101.0 123.4

80.4

 

105.0 105.0 107.9

98.9

117.8

78.0

 

90

122.3

122.3

123.5

122.3

133.8

100.7

 

118.6

118.6

118.7

118.7

128.8

98.7

114.7

114.7

114.8

114.8 123.7

96.8

 

110.7 110.7 110.8

110.8 118.3

94.7

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat.

To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity

SHC = Sensible Heat Capacity

Table PD-5 — Gross Cooling Capacities (kW) TTA100A Condensing Unit withTWE100A Air Handler

 

 

 

 

(SI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29.4

 

 

 

 

35.0

 

 

 

 

40.6

 

 

 

 

46.1

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°C)

 

 

 

 

 

 

 

 

 

 

 

m3/h

Bulb

 

 

16.1

19.4

22.8

16.1

 

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

 

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC TGC SHC TGC SHC

TGC SHC

TGC SHC TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

 

24

30.7

23.9

33.9

20.1

37.4

13.7

29.5

23.3

32.7

19.6

36.0

13.2

28.3

22.7

31.4

19.0

34.6

12.7

27.1

22.1

30.0

18.5

33.1

12.2

5139

27

30.8

27.8

34.0

23.0

37.4

17.9

29.7

27.3

32.8

22.5

36.1

17.4

28.5

26.7

31.5

22.0

34.6

16.8

27.3

26.1

30.1

21.4

33.2

16.3

 

29

31.3

31.3

34.0

26.9

37.5

21.9

30.4

30.4

32.8

26.4

36.2

21.4

29.4

29.4

31.5

25.8

34.7

20.9

28.4

28.4

30.2

25.2

33.3

20.3

 

32

32.9

32.9

34.2

30.9

37.6

26.0

31.9

31.9

33.0

30.3

36.2

25.5

30.9

30.9

31.8

29.8

34.8

24.9

29.9

29.9

30.5

29.2

33.3

24.3

 

24

31.3

25.0

34.5

19.7

38.0

13.9

30.1

24.4

33.3

19.1

36.6

13.5

28.9

23.8

31.9

18.6

35.1

12.9

27.6

23.1

30.5

18.0

33.5

12.4

5692

27

31.5

29.3

34.6

24.0

38.1

18.5

30.3

28.7

33.4

23.5

36.7

17.9

29.2

28.1

32.0

23.0

35.2

17.4

27.9

27.5

30.6

22.3

33.7

16.8

 

29

32.3

32.3

34.7

28.3

38.1

22.9

31.4

31.4

33.4

27.7

36.8

22.3

30.3

30.3

32.1

27.1

35.3

21.8

29.3

29.3

30.7

26.5

33.8

21.3

 

32

34.0

34.0

34.9

32.6

38.2

27.2

33.0

33.0

33.7

32.0

36.8

26.6

31.9

31.9

32.4

31.4

35.3

26.1

30.9

30.9

31.1

30.9

33.8

25.5

 

24

31.8

26.0

35.1

20.3

38.5

14.2

30.6

25.4

33.7

19.7

37.0

13.7

29.3

24.8

32.4

19.2

35.5

13.2

28.0

24.1

30.9

18.6

33.9

12.6

6244

27

32.1

30.6

35.2

25.0

38.6

19.0

30.9

30.1

33.8

24.4

37.1

18.5

29.7

29.5

32.4

23.8

35.6

17.9

28.4

28.4

31.0

23.2

34.1

17.4

 

29

33.2

33.2

35.2

29.5

38.7

23.7

32.2

32.2

33.9

28.9

37.2

23.2

31.2

31.2

32.6

28.4

35.8

22.7

30.0

30.0

31.2

27.8

34.2

22.1

 

32

35.0

35.0

35.6

34.2

38.7

28.3

33.9

33.9

34.3

33.7

37.3

27.8

32.8

32.8

32.8

32.8

35.8

27.2

31.7

31.7

31.7

31.7

34.3

26.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

32.2

27.0

35.5

20.9

38.9

14.4

31.0

26.4

34.2

20.3

37.4

13.9

29.7

25.7

32.8

19.8

35.8

13.3

28.4

25.1

31.3

19.2

34.2

12.8

6796

27

32.6

32.0

35.6

25.8

39.0

19.5

31.5

31.4

34.2

25.2

37.5

19.0

30.2

30.2

32.8

24.6

36.0

18.4

29.1

29.1

31.4

24.0

34.4

17.9

 

29

34.0

34.0

35.7

30.7

39.1

24.6

33.0

33.0

34.4

30.2

37.7

24.1

31.9

31.9

33.0

29.6

36.1

23.5

30.7

30.7

31.6

29.0

34.5

22.8

 

32

35.8

35.8

36.2

35.8

39.2

29.5

34.7

34.7

34.8

34.8

37.7

28.9

33.6

33.6

33.6

33.6

36.2

28.3

32.4

32.4

32.4

32.4

34.6

27.7

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity SHC = Sensible Heat Capacity

18

SS-PRC003-EN

Page 18
Image 18
Trane SS-PRC003-EN manual Performance, DataSystem, AmbientTemperature F