Trane SS-PRC003-EN manual Performance, DataSystem, Table PD-1- Gross Cooling Capacities kW

Models: SS-PRC003-EN

1 79
Download 79 pages 17.04 Kb
Page 14
Image 14
Performance

Performance

DataSystem

Table PD-1 — Gross Cooling Capacities (MBh) TTA075A Condensing Unit withTWE075A Air Handler

 

 

 

 

(I-P)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

95

 

 

 

 

 

105

 

 

 

 

115

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°F)

 

 

 

 

 

 

 

 

 

 

 

CFM

Bulb

 

 

61

67

73

61

 

67

 

73

 

61

 

67

73

61

 

67

 

73

 

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC TGC SHC TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

TGC SHC TGC SHC TGC SHC

 

75

77.2

60.6

85.4

50.9

94.1

34.7

74.8

59.4

82.6

49.8

90.9

33.6

71.8

57.9

79.3

48.4

87.2

32.3

68.4

56.2

75.5

46.9

83.0

30.8

2250

80

77.6

70.5

85.6

58.4

94.2

45.3

75.2

69.3

82.8

57.2

91.0

44.1

72.3

67.9

79.5

55.8

87.3

42.7

69.0

66.2

75.6

54.0

83.2

41.2

 

85

79.1

79.1

85.7

68.3

94.3

55.6

77.0

77.0

83.0

67.0

91.2

54.4

74.6

74.6

79.6

65.6

87.5

53.0

71.7

71.7

75.9

63.9

83.4

51.5

 

90

83.1

83.1

86.1

78.3

94.5

65.9

81.0

81.0

83.4

77.1

91.2

64.5

78.4

78.4

80.2

75.6

87.6

63.0

75.4

75.4

76.6

74.0

83.5

61.4

 

75

78.8

63.4

87.0

49.9

95.7

35.4

76.2

62.1

84.1

48.7

92.4

34.2

73.2

60.6

80.7

47.2

88.5

32.9

69.6

58.9

76.7

45.6

84.2

31.4

2500

80

79.3

74.3

87.2

61.1

95.8

46.8

76.8

73.1

84.2

59.7

92.5

45.6

73.9

71.6

80.8

58.2

88.7

44.2

70.5

70.0

76.9

56.4

84.4

42.6

 

85

81.7

81.7

87.4

71.8

96.0

58.1

79.6

79.6

84.5

70.5

92.7

56.8

77.0

77.0

81.0

69.0

88.9

55.4

73.9

73.9

77.2

67.3

84.6

53.9

 

90

85.9

85.9

87.9

82.8

96.0

69.0

83.7

83.7

85.2

81.5

92.7

67.7

80.9

80.9

81.9

80.0

89.0

66.2

77.8

77.8

77.8

77.8

84.8

64.5

 

75

80.1

66.1

88.3

51.5

97.0

36.0

77.5

64.8

85.3

50.3

93.5

34.8

74.3

63.2

81.8

48.8

89.6

33.4

70.7

61.5

77.7

47.2

85.2

31.8

2750

80

80.9

78.0

88.4

63.4

97.1

48.2

78.3

76.7

85.5

62.1

93.7

47.0

75.3

75.2

81.9

60.5

89.8

45.6

71.9

71.9

77.9

58.8

85.4

44.0

 

85

84.1

84.1

88.7

75.1

97.3

60.4

81.8

81.8

85.7

73.8

93.9

59.1

79.0

79.0

82.3

72.2

90.0

57.7

75.8

75.8

78.3

70.5

85.5

55.9

 

90

88.4

88.4

89.6

87.1

97.4

72.0

86.0

86.0

86.8

85.8

94.0

70.7

83.1

83.1

83.2

83.2

90.1

69.2

79.8

79.8

79.9

79.9

85.8

67.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

81.3

68.6

89.5

53.1

98.0

36.5

78.5

67.3

86.4

51.9

94.5

35.2

75.3

65.7

82.7

50.4

90.5

33.8

71.6

63.9

78.6

48.7

85.9

32.2

3000

80

82.3

81.5

89.6

65.7

98.2

49.6

79.4

79.4

86.5

64.4

94.7

48.3

76.6

76.6

82.9

62.8

90.7

46.9

73.5

73.5

78.8

61.1

86.3

45.3

 

85

86.1

86.1

89.9

78.3

98.4

62.6

83.7

83.7

86.9

76.9

94.9

61.3

80.8

80.8

83.4

75.4

90.8

59.6

77.5

77.5

79.4

73.7

86.4

57.9

 

90

90.5

90.5

90.6

90.6

98.5

75.0

88.0

88.0

88.1

88.1

95.0

73.6

85.0

85.0

85.1

85.1

91.1

72.1

81.6

81.6

81.7

81.7

86.7

70.4

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat.

To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity

SHC = Sensible Heat Capacity

Table PD-1 — Gross Cooling Capacities (kW)

TTA075A Condensing Unit withTWE075A Air Handler

 

 

 

 

(SI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29.4

 

 

 

 

35.0

 

 

 

 

40.6

 

 

 

 

46.1

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°C)

 

 

 

 

 

 

 

 

 

 

 

m3/h

Bulb

 

 

16.1

19.4

22.8

16.1

 

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

 

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC TGC SHC TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

TGC SHC TGC SHC TGC SHC

 

24

22.6

17.7

25.0

14.9

27.6

10.2

21.9

17.4

24.2

14.6

26.6

9.8

21.0

16.9

23.2

14.2

25.5

9.5

20.0

16.5

22.1

13.7

24.3

9.0

3823

27

22.7

20.7

25.1

17.1

27.6

13.3

22.0

20.3

24.3

16.8

26.6

12.9

21.2

19.9

23.3

16.3

25.6

12.5

20.2

19.4

22.1

15.8

24.3

12.1

 

29

23.2

23.2

25.1

20.0

27.6

16.3

22.6

22.6

24.3

19.6

26.7

15.9

21.8

21.8

23.3

19.2

25.6

15.5

21.0

21.0

22.2

18.7

24.4

15.1

 

32

24.3

24.3

25.2

22.9

27.7

19.3

23.7

23.7

24.4

22.6

26.7

18.9

23.0

23.0

23.5

22.1

25.6

18.5

22.1

22.1

22.4

21.7

24.4

18.0

 

24

23.1

18.6

25.5

14.6

28.0

10.4

22.3

18.2

24.6

14.3

27.0

10.0

21.4

17.7

23.6

13.8

25.9

9.6

20.4

17.2

22.5

13.4

24.7

9.2

4248

27

23.2

21.8

25.5

17.9

28.0

13.7

22.5

21.4

24.7

17.5

27.1

13.3

21.6

21.0

23.7

17.0

26.0

12.9

20.7

20.5

22.5

16.5

24.7

12.5

 

29

23.9

23.9

25.6

21.0

28.1

17.0

23.3

23.3

24.7

20.6

27.1

16.6

22.5

22.5

23.7

20.2

26.0

16.2

21.6

21.6

22.6

19.7

24.8

15.8

 

32

25.2

25.2

25.8

24.2

28.1

20.2

24.5

24.5

24.9

23.9

27.2

19.8

23.7

23.7

24.0

23.4

26.1

19.4

22.8

22.8

22.8

22.8

24.8

18.9

 

24

23.5

19.3

25.9

15.1

28.4

10.5

22.7

19.0

25.0

14.7

27.4

10.2

21.8

18.5

23.9

14.3

26.2

9.8

20.7

18.0

22.8

13.8

24.9

9.3

4672

27

23.7

22.8

25.9

18.6

28.4

14.1

22.9

22.5

25.0

18.2

27.4

13.8

22.1

22.0

24.0

17.7

26.3

13.3

21.0

21.0

22.8

17.2

25.0

12.9

 

29

24.6

24.6

26.0

22.0

28.5

17.7

24.0

24.0

25.1

21.6

27.5

17.3

23.1

23.1

24.1

21.2

26.3

16.9

22.2

22.2

22.9

20.7

25.0

16.4

 

32

25.9

25.9

26.2

25.5

28.5

21.1

25.2

25.2

25.4

25.1

27.5

20.7

24.3

24.3

24.4

24.4

26.4

20.3

23.4

23.4

23.4

23.4

25.1

19.8

 

24

23.8

20.1

26.2

15.5

28.7

10.7

23.0

19.7

25.3

15.2

27.7

10.3

22.0

19.2

24.2

14.8

26.5

9.9

21.0

18.7

23.0

14.3

25.2

9.4

5097

27

24.1

23.9

26.2

19.2

28.8

14.5

23.2

23.2

25.3

18.8

27.7

14.1

22.4

22.4

24.3

18.4

26.6

13.7

21.5

21.5

23.1

17.9

25.3

13.3

 

29

25.2

25.2

26.3

22.9

28.8

18.3

24.5

24.5

25.4

22.5

27.8

18.0

23.7

23.7

24.4

22.1

26.6

17.5

22.7

22.7

23.2

21.6

25.3

17.0

 

32

26.5

26.5

26.5

26.5

28.8

22.0

25.8

25.8

25.8

25.8

27.8

21.6

24.9

24.9

24.9

24.9

26.7

21.1

23.9

23.9

23.9

23.9

25.4

20.6

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat.

To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity

SHC = Sensible Heat Capacity