Table PD-14 — Gross Cooling Capacities (MBh) - Single Compressor -TTA155C Condensing Unit withTWE155B Air Handler (I-P)

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

 

 

95

 

 

 

 

 

105

 

 

 

 

 

115

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°F)

 

 

 

 

 

 

 

 

 

 

 

 

CFM

Bulb

 

 

61

67

73

 

61

 

67

73

 

61

 

67

 

73

 

61

 

67

 

73

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

(°F)

TGC

SHC

TGC

SHC

TGC

SHC

 

TGC

SHC

TGC

SHC

TGC SHC

 

TGC SHC TGC SHC

TGC SHC

 

TGC SHC TGC SHC TGC SHC

 

75

94.3

92.3

103.0

67.8

112.7

43.8

 

91.7

91.0

99.8

66.5

108.7

42.4

 

88.2

88.2

96.0

64.8

104.3

41.0

 

84.6

84.6

91.6

62.9

99.3

39.4

4500

80

99.4

99.4

103.6

87.7

113.5

63.2

 

96.8

96.8

100.4

86.4

109.6

61.8

 

93.7

93.7

96.6

84.8

105.3

60.1

 

90.0

90.0

92.3

83.0

100.6

58.3

 

85

105.3

105.3

105.4

105.4

114.2

83.1

 

102.5

102.5

102.6

102.6

110.4

81.7

 

99.2

99.2

99.3

99.3

106.1

80.1

 

95.4

95.4

95.5

95.5

101.4

78.3

 

90

111.3

111.3

111.5

111.5

114.8

103.2

 

108.4

108.4

108.5

108.5

111.2

101.9

 

104.9 104.9 105.0 105.0

107.0

100.3

 

100.9 100.9 101.0 101.0 102.3

98.5

 

75

95.8

95.8

104.2

72.0

113.7

43.9

 

93.3

93.3

100.9

70.8

109.5

42.6

 

90.1

90.1

97.0

69.3

105.0

41.1

 

86.4

86.4

92.5

65.6

100.0

39.5

5000

80

101.8

101.8

104.9

92.4

114.9

66.6

 

99.1

99.1

101.6

91.1

110.9

65.3

 

95.8

95.8

97.8

89.5

106.5

63.9

 

92.0

92.0

93.4

87.6

101.6

62.3

 

85

107.9

107.9

108.0

108.0

115.4

87.3

 

105.0

105.0

105.0

105.0

111.6

85.9

 

101.5 101.5 101.6 101.6

107.2

84.3

 

97.6

97.6

97.6

97.6

102.3

82.5

 

90

114.1

114.1

114.3

114.3

116.3

109.4

 

111.0

111.0

111.1

111.1

112.6

108.1

 

107.4 107.4 107.5 107.5

108.4

106.5

 

103.3 103.3 103.4 103.4 103.5

103.5

 

75

97.7

97.7

105.2

73.3

114.5

44.7

 

95.0

95.0

101.8

71.9

110.2

43.4

 

91.8

91.8

97.8

70.2

105.6

41.9

 

88.0

88.0

93.2

68.2

100.4

40.3

5500

80

103.8

103.8

106.0

97.0

115.8

69.3

 

101.0

101.0

102.7

95.6

111.8

68.0

 

97.6

97.6

98.8

94.0

107.3

66.5

 

93.6

93.6

94.4

92.1

102.4

64.9

 

85

110.1

110.1

110.2

110.2

116.4

91.5

 

107.0

107.0

107.1

107.1

112.5

90.0

 

103.4 103.4 103.5 103.5

108.1

88.4

 

99.4

99.4

99.4

99.4

103.1

86.5

 

90

116.5

116.5

116.6

116.6

117.6

115.4

 

113.3

113.3

113.4

113.4

113.5

113.5

 

109.5 109.5 109.6 109.6

109.7

109.7

 

105.3 105.3 105.4 105.4 105.5

105.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

99.3

99.3

106.0

75.9

115.1

45.5

 

96.6

96.6

102.6

74.5

110.7

44.1

 

93.2

93.2

98.5

72.7

106.1

42.6

 

89.3

89.3

93.9

70.7

100.8

41.0

6000

80

105.6

105.6

107.0

101.4

116.6

71.8

 

102.6

102.6

103.7

100.0

112.5

70.5

 

99.1

99.1

99.8

98.3

107.9

69.1

 

95.1

95.1

95.1

95.1

103.0

67.5

 

85

112.0

112.0

112.1

112.1

117.2

95.5

 

108.9

108.9

109.0

109.0

113.3

94.0

 

105.2 105.2 105.2 105.2

108.8

92.3

 

101.0 101.0 101.0 101.0 103.9

90.5

 

90

118.5

118.5

118.6

118.6

118.7

118.7

 

115.2

115.2

115.3

115.3

115.4

115.4

 

111.4 111.4 111.5 111.5

111.5

111.5

 

107.0 107.0 107.1 107.1 107.2

107.2

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat.

To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity

SHC = Sensible Heat Capacity

Table PD-14 — Gross Cooling Capacities (kW) - Single Compressor - TTA155C Condensing Unit withTWE155B Air Handler

(SI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AmbientTemperature (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29.4

 

 

 

 

35.0

 

 

 

 

40.6

 

 

 

 

46.1

 

 

 

Enter.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry

 

 

 

 

 

 

 

 

 

 

 

Entering Wet Bulb (°C)

 

 

 

 

 

 

 

 

 

 

 

m3/h

Bulb

 

 

16.1

19.4

22.8

16.1

 

19.4

22.8

16.1

19.4

22.8

16.1

19.4

22.8

 

Airflow

(°C)

TGC

SHC

TGC

SHC

TGC

SHC

TGC

SHC TGC SHC TGC SHC

TGC SHC

TGC SHC TGC SHC

TGC SHC

TGC

SHC

TGC

SHC

 

24

27.6

27.0

30.2

19.9

33.0

12.8

26.8

26.7

29.2

19.5

31.8

12.4

25.8

25.8

28.1

19.0

30.5

12.0

24.8

24.8

26.8

18.4

29.1

11.6

7646

27

29.1

29.1

30.3

25.7

33.2

18.5

28.4

28.4

29.4

25.3

32.1

18.1

27.4

27.4

28.3

24.8

30.8

17.6

26.3

26.3

27.0

24.3

29.4

17.1

 

29

30.8

30.8

30.9

30.9

33.4

24.3

30.0

30.0

30.1

30.1

32.3

23.9

29.1

29.1

29.1

29.1

31.1

23.4

27.9

27.9

28.0

28.0

29.7

22.9

 

32

32.6

32.6

32.6

32.6

33.6

30.2

31.7

31.7

31.8

31.8

32.6

29.8

30.7

30.7

30.7

30.7

31.3

29.4

29.6

29.6

29.6

29.6

30.0

28.9

 

24

28.0

28.0

30.5

21.1

33.3

12.9

27.3

27.3

29.6

20.7

32.1

12.5

26.4

26.4

28.4

20.3

30.8

12.0

25.3

25.3

27.1

19.2

29.3

11.6

8495

27

29.8

29.8

30.7

27.1

33.6

19.5

29.0

29.0

29.8

26.7

32.5

19.1

28.0

28.0

28.6

26.2

31.2

18.7

26.9

26.9

27.3

25.7

29.8

18.2

 

29

31.6

31.6

31.6

31.6

33.8

25.6

30.7

30.7

30.8

30.8

32.7

25.2

29.7

29.7

29.7

29.7

31.4

24.7

28.6

28.6

28.6

28.6

30.0

24.2

 

32

33.4

33.4

33.5

33.5

34.0

32.0

32.5

32.5

32.5

32.5

33.0

31.6

31.4

31.4

31.5

31.5

31.7

31.2

30.2

30.2

30.3

30.3

30.3

30.3

 

24

28.6

28.6

30.8

21.5

33.5

13.1

27.8

27.8

29.8

21.1

32.3

12.7

26.9

26.9

28.6

20.6

30.9

12.3

25.8

25.8

27.3

20.0

29.4

11.8

9345

27

30.4

30.4

31.0

28.4

33.9

20.3

29.6

29.6

30.1

28.0

32.7

19.9

28.6

28.6

28.9

27.5

31.4

19.5

27.4

27.4

27.6

27.0

30.0

19.0

 

29

32.2

32.2

32.3

32.3

34.1

26.8

31.3

31.3

31.4

31.4

32.9

26.4

30.3

30.3

30.3

30.3

31.6

25.9

29.1

29.1

29.1

29.1

30.2

25.3

 

32

34.1

34.1

34.1

34.1

34.4

33.8

33.2

33.2

33.2

33.2

33.2

33.2

32.1

32.1

32.1

32.1

32.1

32.1

30.8

30.8

30.9

30.9

30.9

30.9

 

24

29.1

29.1

31.0

22.2

33.7

13.3

28.3

28.3

30.0

21.8

32.4

12.9

27.3

27.3

28.8

21.3

31.1

12.5

26.1

26.1

27.5

20.7

29.5

12.0

10194

27

30.9

30.9

31.3

29.7

34.1

21.0

30.1

30.1

30.4

29.3

32.9

20.6

29.0

29.0

29.2

28.8

31.6

20.2

27.8

27.8

27.9

27.9

30.1

19.8

 

29

32.8

32.8

32.8

32.8

34.3

28.0

31.9

31.9

31.9

31.9

33.2

27.5

30.8

30.8

30.8

30.8

31.9

27.0

29.6

29.6

29.6

29.6

30.4

26.5

 

32

34.7

34.7

34.7

34.7

34.7

34.7

33.7

33.7

33.8

33.8

33.8

33.8

32.6

32.6

32.6

32.6

32.7

32.7

31.3

31.3

31.4

31.4

31.4

31.4

Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.

All capacities shown are gross and have not considered indoor fan heat.

To obtain net cooling capacities subtract indoor fan heat.

TGC = Total Gross Cooling Capacity

SHC = Sensible Heat Capacity