Trane TAM7A0B30H21SB, TAM7A0C60H51SB, TAM7A0C48H41SB, TAM7B0C60H51SA Field Wiring, Two Stage HP

Models: TAM7A0C36H31SB TAM7A0C42H31SB TAM7A0C48H41SB TAM7B0C60H51SA TAM7A0B30H21SB TAM7A0C60H51SB

1 28
Download 28 pages 33.03 Kb
Page 23
Image 23
Two Stage HP

Field

Wiring

Two Stage HP

Heat Pump

Comfort Control

 

X2

 

W

White

G

Green

Y1

Yellow

O

Orange

R

Red

B

Blue

Y2

Brown

Field wiring

 

Neatly bundle all low voltage wires behind the service valve cover as shown.

Air Handler

Black

(X2)

Yellow

Yellow/Red

W3 *

 

 

Red

Blue

W2

W1 - White

Orange

 

 

W1

 

 

 

BK

 

 

 

 

G

 

 

 

 

Y2

Y2 - Brown

 

 

 

YI (In)

O - Orange

 

 

 

O

 

 

 

R

R - Red

 

 

 

B

B - Blue

 

 

 

YO (Out)

Y1 - Yellow

 

 

 

•• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat

•• YI and YO connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly

•• Internally mounted condensate switch is optional and must be ordered separately

•• If a 3rd party condensate overflow switch is installed, it should be wired in series between YO and Y to the outdoor unit