Trane DX1C100A9H31B, UX1C100A9H41B manual Horizontal Venting, Vent and Inlet AIR Connections

Models: UX1B060A9H31B DX1B040A9H21B DX1B060A9H31B DX1B080A9H31B UX1B040A9H21B UX1B080A9H31B UX1C100A9H41B DX1D120A9H51B UX1D120A9H51B DX1C100A9H31B

1 38
Download 38 pages 49.52 Kb
Page 16
Image 16

Installer’s Guide

VENT AND INLET AIR CONNECTIONS

p

 

 

Seal VENT PIPE

 

 

 

 

 

 

 

 

with RTV sealant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front of Furnace

Seal INLET AIR PIPE

with RTV sealant

NOTE:

Follow venting instructions carefully when using PVC cement.

IMPORTANT:

WHEN THE FACTORY SUPPLIED "OFF-SET" (2X3 REDUCING COUPLING) IS USED FOR 3" VENT PIPE INSTALLATION, MAKE SURE THE MARKING "TOP" IS

LOCATED ON THE TOP SIDE OF THE PIPE.

a

 

LABEL

 

SAYS

 

"TOP"

 

STRAIGHT SIDE MUST BE

ON BOTTOM FOR PROPER

CONDENSATE DRAINAGE.

All joints must be water tight. Flue condensate is some- what acidic, and leaks can cause equipment damage.

Connection of the pipe and collar of the combustion air inlet should just be a friction fit. It is recommended that the inlet air joint be sealed with RTV type sealant to allow the joint to be separated for possible future ser- vice. The inlet and vent pipes must be properly sup- ported throughout the entire length.

Connection of the vent pipe to the vent collar should also be accomplished using RTV type sealant. This type sealant provides a connection which remains flexible and can be separated in the future if service needs re- quire the removal of the vent pipe for service or clear- ance.

NOTE:

s

2" TO 3" COUPLING

#CPL00838

FACTORY SUPPLIED ONLY WITH THE FOLLOWING MODELS:

UC120 & DC120

UX120 & UY120

UX100 & UY100 UX080C960

ALL DX & DY MODLES UX3 & DX3

UH3 & DH3

To ensure proper operation at the vent lengths indi- cated, the combustion air inlet and vent terminals should be in the same pressure zone. Terminating the vent and inlet in different pressure zones will change the maximum vent lengths and may cause nuisance tripping of the pressure switch(es). The amount of change can not be predicted. The selection of the inlet and outlet terminal locations are the responsibility of the designer/installer. If the installer chooses separate pressure zones for the terminals, the combustion air inlet termination must be in the higher (more positive) pressure zone.

HORIZONTAL VENTING

NOTE:

Vent termination kit BAYAIR30AVENTA or BAYVENT200B may be used instead of the horizontal and vertical termination options shown in the follow- ing figures.

FURNACE

VENT

OUTLET

HORIZONTAL INSTALLATION

(Upflow/ Horizontal or Downflow/ Horizontal)

NOTE:

In horizontal venting when the factory supplied “off- set” (2X3 reducing coupling) is used for 3” vent pipe installation, make sure the marking “Top” is located on the top side of the pipe. The straight side must be on bottom for proper condensate drainage. This coupling is factory supplied only with the following models: *UC120 & *DC120, *UX120 & *UY120 *UX100 & *UY100, *UX808C960, and all *DX & *DY models.

16

18-CD22D1-8

Page 16
Image 16
Trane DX1C100A9H31B, UX1C100A9H41B, UX1B080A9H31B, UX1B060A9H31B manual Horizontal Venting, Vent and Inlet AIR Connections