Installer’s Guide

 

 

 

TWINNING CONNECTION DIAGRAM

 

 

 

FOR TWINNING 1 STAGE FURNACES WITH

 

 

 

 

SINGLE WIRE TWINNING FEATURE

 

 

1 STAGE

1 STAGE HEAT / 1 STAGE COOL THERMOSTAT

 

OUTDOOR UNIT

 

 

 

 

HEATING / COOLING

 

 

 

 

(WITH TRANSFORMER)

 

 

 

 

THERMOSTAT

 

FURNACE NO. 1

FURNACE NO. 2

 

 

 

 

 

 

 

 

BLOWER OPERATION OF

 

 

 

 

 

UNIT NO. 2 IS SYNCRONIZED

 

 

 

 

 

WITH UNIT NO. 1 VIA SIGNALS

 

 

 

 

 

FROM TWIN CONNECTION.

 

 

 

 

TWIN

TWIN

 

RC

 

 

 

 

 

ISOLATION RELAY

 

 

 

 

 

(FIELD SUPPLIED)

 

 

 

 

 

SEE NOTE 3

 

 

 

 

 

 

 

 

 

SEE NOTE 4

 

OUTDOOR UNIT

 

 

 

 

 

(NO TRANSFORMER)

 

 

 

 

 

 

 

 

 

 

R1

 

 

 

 

 

ISOLATION RELAY

 

 

 

 

 

SEE NOTE 4

 

 

SEE NOTE 5

B/C

R1

 

 

B/C

B/C

 

 

 

 

 

 

 

 

ISOLATION RELAY

 

 

 

 

 

(FIELD SUPPLIED)

 

 

 

 

 

SEE NOTE 4

From Dwg. 21B341423 Rev. 2

 

 

 

 

 

GAS PIPING

The upflow/ horizontal furnace is shipped standard for left side installation of gas piping. A knockout is pro- vided on the right side for an alternate gas piping ar- rangement. See Figure 37.

The installation of piping shall be in accordance with piping codes and the regulations of the local gas com- pany. Pipe joint compound must be resistant to the chemical reaction with liquefied petroleum gases.

Refer to piping Table 10, for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual shut-off valve as shown in Figures 37-39.

National codes require a condensation drip leg to be in- stalled ahead of the controls as shown in Figures 37-39. The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

The furnace must be isolated from the gas supply piping by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

NOTE:

Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.

All gas fittings must be checked for leaks using a soapy solution before lighting the furnace. DO NOT CHECK WITH AN OPEN FLAME!

18-CD22D1-8

29

Page 29
Image 29
Trane DX1B080A9H31B, UX1C100A9H41B, UX1B080A9H31B, UX1B060A9H31B manual GAS Piping, Stage Heat / 1 Stage Cool Thermostat