XT302C DELUXE PROGRAMMABLE HEAT-COOL  THERMOSTAT
DEVICE INFORMATION
SELF-TEST  (70)
1. Press Temp ▲ and ▼ keys simultaneously, then press Time ▼ to access the thermostat information.
M4934
2. Press Increase ▲ to display the production date code
in a 
M17112
3. Press Increase ▲ again to display the software identification code.
(Example: 200 = software ID code 200)
M17113
4. Press Increase ▲ again to display the software revision number (Example: 001=Revision number 1).
M10229
5. Press the Increase ▲ again to display the model identification number. (Example: 314 = Model ID 314)
M4933A
6. Press Run Program to exit the 
mode times out 5 minutes after the last key press.
CHECKOUT
Outdoor Temperature Sensor (optional accessory)
Expose the outdoor temperature to outdoor air for a minimum of five minutes before reading.
TROUBLESHOOTING GUIDE
| Symptom | Possible Cause | Action | |
| 
 | 
 | 
 | |
| Display will not come | Thermostat is not being | Check for 24 Vac between R and W terminals. | |
| on. | powered. | Check if the circuit breaker is  | |
| 
 | 
 | Check if the system fuse is  | |
| 
 | 
 | Check if the power switch on the HVAC equipment is in the | |
| 
 | 
 | Off  | |
| 
 | 
 | Check wiring between thermostat and HVAC  | |
| 
 | 
 | broken wires and tighten any loose connections. | |
| 
 | 
 | If 24 Vac is present, proceed with troubleshooting. | |
| 
 | 
 | 
 | |
| Temperature display is | Room temperature | Enter Installer Setup number 37 and reconfigure the display. | |
| incorrect. | display has been | 
 | |
| 
 | reconfigured. | 
 | |
| 
 | 
 | 
 | |
| 
 | Thermostat is configured | Enter Installer Setup number 14 and reconfigure the display. | |
| 
 | for °F or °C display. | 
 | |
| 
 | Bad thermostat location. | Relocate the thermostat. | |
| 
 | 
 | 
 | |
| Temperature | Internal temperature | Contact distributor or retailer. | |
| displaying digits as | measurement failure. | 
 | |
| dashes  | 
 | 
 | |
| 
 | 
 | 
 | |
| Temperature settings | The upper or lower | Check the temperature setpoints: | |
| will not change. | temperature limits were | Heating limits are 55 to 85°F (13 to 29°C). | |
| (Example: | reached. | Cooling limits are 65 to 99°F (18 to 37°C). | |
| Cannot set the | The setpoint temperature | Check Installer Setup numbers 34 and 35 and reconfigure the | |
| heating higher or the | range stops were | setpoint stops. | |
| cooling lower.) | |||
| configured. | 
 | ||
| 
 | 
 | ||
| 
 | 
 | 
 | |
| 
 | 
 | (continued) | |