XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

To advance to the next Installer Setup, press Time ▲.

To change a setting, press Increase ▲ or Decrease ▼.

To scroll the Installer Setup numbers backwards, press Time ▼.

To exit the Installer Setup, press Run Program.

CAUTION

Equipment Damage Hazard.

Can cause permanent equipment damage. Electric heat systems must be configured to 1 in Installer Setup number 2 to prevent equipment damage caused by the system running without the fan.

IMPORTANT

Only configurable numbers display. Example: Installer Setup Number 1 does not display because it is not configurable. Review the factory settings in Table 3 and make any desired changes in the Actual Settings column. When the Installer Setup is complete, review the settings to confirm that they match the system and the boxes you checked in the Customizing Your Thermostat chart located in the Owners Guide.

Table 3. Installer Setup Options for the XT302C.

 

Press Time

 

Press Increase or Decrease to change setting

 

 

or

 

 

 

Installer

Factory Setting

 

Other Choices

Actual

 

 

 

 

 

 

 

 

Select

Setup Number

Display

 

Description

Display

Description

Setting

Programming

42

0

 

7-day programming

1 or 2

1—24-hour programming

 

 

Press Time to

 

 

 

 

2—No programming

 

 

bypass 2–41

 

 

 

 

 

 

 

and go directly

 

 

 

 

 

 

 

to setup #42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan operation

2

0

 

Conventional

1

Applications where

 

 

 

 

 

applications where

 

thermostat controls fan

 

 

 

 

 

equipment controls

 

operation in heat mode

 

 

 

 

 

fan operation in heat

 

 

 

 

 

 

 

mode

 

 

 

 

 

 

 

 

 

 

 

Number of

3

2

 

2 heating stages

0 or 1

0—no heating

 

heating Stages

 

 

 

 

 

1—1 heating stage

 

 

 

 

 

 

 

 

 

Stage 1 heating

4

3

 

3—3 cph

5, 6, or 9

5—5 cph

 

cycle rate

 

 

 

recommended 5, 6, or

 

6—6 cph

 

 

 

 

 

9 cph not

 

9—9 cph

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

Stage 2 heating

5

5

 

5—5 cph

3, 6, or 9

3—3 cph

 

cycle rate

 

 

 

recommended

 

6—6 cph

 

 

 

 

 

3, 6, or 9 cph not

 

9—9 cph

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

Number of

8

1

 

1 cooling stage

0 or 2

0—no cooling

 

Cooling Stages

 

 

 

 

 

2—2 cooling stages

 

 

 

 

 

 

 

 

 

Stage 1 cooling

9

3

 

3—3 cph

2 or 5

2—2 cph

 

cycle rate

 

 

 

recommended

 

5—5 cph

 

 

 

 

 

2 or 5 cph not

 

 

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

Stage 2 cooling

10

3

 

3—3 cph

2 or 5

2—2 cph

 

cycle rate

 

 

 

recommended

 

5—5 cph

 

 

 

 

 

2 or 5 cph not

 

 

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

System setting

12

0

 

Auto changeover

1 or 2

1—Manual changeover

 

adjustment

 

 

 

 

 

2—Auto changeover only

 

 

 

 

 

 

 

 

 

(continued)

Pub. No. 18-HD25D7-5

5

69-1213—1 (T8624)

Page 5
Image 5
Trane XT302C manual Press Time to, Bypass Go directly To setup #42, Cph not, Or 9 cph not, Or 5 cph not Recommended