XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

 

 

 

 

 

 

 

 

Table 5. Installer Self-Test Options.

 

 

 

 

 

Key to

Test

 

 

 

Press

Number

Description

 

 

 

 

 

 

 

Heating Equipment Self-Test (10)

 

 

 

 

 

 

Time ▲

10

 

Enter heating equipment self-test.

 

 

 

 

Temp ▲

11

 

First stage heat turns on. When Installer Setup number 2 is 1, the system fan is also energized.

 

 

 

 

 

Temp ▲

12

 

Second stage heat

turns on.

 

 

 

 

 

Temp ▼

11

 

Second stage heat

turns off.

 

 

 

 

Temp ▼

10

 

First stage heat turns off.

 

 

 

 

 

Cooling Equipment Self-Test (30)

 

 

 

 

 

 

Time ▲

30

 

Enter cooling equipment self-test.

 

 

 

 

Temp ▲

31

 

First stage cool and fan turn on.

 

 

 

 

 

Temp ▲

32

 

Second stage cool

turns on.

 

 

 

 

 

Temp ▲

31

 

Second stage cool

turns off.

 

 

 

 

Temp ▼

30

 

First stage cool and fan turn off.

 

 

 

 

 

Fan Equipment Self-Test (40)

 

 

 

 

 

 

Time ▲

40

 

Enter fan equipment self-test.

 

 

 

 

 

 

Temp ▲

41

 

Fan turns on.

 

 

 

 

 

 

 

 

Temp ▼

40

 

Fan turns off.

 

 

 

 

 

 

 

Comfort-R Terminals Self-Test (50)

 

 

 

 

 

 

Temp ▲

50

 

Enter Comfort-R self-test.

 

 

 

 

Temp ▼

51

 

Reads HH terminals. If the terminals are open and Comfort-R is enabled, display reads

 

 

 

% humidity. If the terminals are closed no % humidity displays.

 

 

 

 

 

Keyboard Operation Self-Test (60)

 

 

 

 

 

 

Time ▲

60

7

Enter keyboard operation self-test.

 

 

 

 

Temp ▲

60

9

Increase test number displays.

 

 

 

 

Temp ▼

60

8

Decrease test number displays.

 

 

 

 

Day

60

11

Day test number displays.

 

 

 

 

Copy

60

12

Copy test number displays.

 

 

 

 

System

60

3

System test number displays.

 

 

 

 

Fan

60

10

Fan test number displays.

 

 

 

 

Set

60

1

Set Current Day/Time test number displays.

Current

 

 

 

 

 

Day/Time

 

 

 

 

 

 

 

 

 

Run

60

15

Run Program test number displays.

Program

 

 

 

 

 

 

 

 

 

Daylight

60

19

Daylight Time test number displays.

Time

 

 

 

 

 

 

 

 

 

Heat/ Cool

60

5

Heat/Cool Settings test number displays.

Settings

 

 

 

 

 

 

 

 

 

Wake

60

0

Wake test number displays.

 

 

 

 

Leave

60

14

Leave test number displays.

 

 

 

 

Return

60

16

Return test number displays.

 

 

 

 

Sleep

60

2

Sleep test number displays.

 

 

 

 

Filter

60

17

Filter test number displays.

i60 13 Information test number displays.

Device Information Self-Test (70) - Refer to following section.

Pub. No. 18-HD25D7-5

9

69-1213—1 (T8624)

Page 9
Image 9
Trane XT302C Installer Self-Test Options, Temp, Cooling Equipment Self-Test Time, Fan Equipment Self-Test Time, Day, Copy