Battery Replacement

Under normal conditions, the original batteries in your UPS will last many years. Battery replacement should be performed only by qualified service personnel. When replacing the batteries, qualified service personnel should refer to “Battery Warnings” in the Safety section and use the following procedure. The batteries are designed for hot-swap replacement, but some users may wish to put the UPS in the OFF mode and disconnect equipment before proceeding. Note: Batteries cartridges are heavy. Replacement may require an assistant.

A

1.Unscrew the six screws on the front face of the unit and remove the front panel. Allow it to dan- gle by the ribbon cable connecting the LED panel to the UPS.

2.Slide the internal battery cartridges partially out of the UPS towards the front until their electri- cal connection (A) may be disconnected.

3.Remove batteries from the UPS completely and dispose of them properly.

4.Examine the detailed connection diagram on the inside surface of the UPS system’s front panel.

5.Connect replacement batteries exactly according to the diagram, making sure that the input and output cables (A) are connected as before, black to black and red to red. Reassemble the UPS by reversing the steps above. Note: your new batteries should be allowed to charge for 2-4 hours before they support a load.

Specifications

Model:

SMART1400RM2U

SMART1500RMXL2U

 

Series:

AGSM1400Y2U29

AGSM1400Y2U29

 

Output Capacity (VA/Watts):

1400/940

1500/940

 

Battery Runtime in Minutes

 

 

 

(Half Load/Full Load):

30+/12+*

30+/12+*

 

Battery Recharge Time:

2-4 hrs.*

2-4 hrs.*

 

Approvals:

UL, cUL, NOM

UL, cUL, NOM

 

Model:

SMART2200RMXL2U

SMART2600RM2U

SMART3000RM2U

Series:

AGSM2200Y2U29

AGSM3000Y2U29

AGSM3000Y2U29

Output Capacity (VA/Watts):

2200/1600

2600/2100

3000/2250

 

(1440/1307

(2200/1787

(2200/1787

 

with 15-amp plug)

with 20-amp plug)

with 20-amp plug)

Battery Runtime in Minutes

 

 

 

(Half Load/Full Load):

20+/8+*

18+/6+*

13+/4+*

Battery Recharge Time:

2-4 hrs.*

2-4 hrs.*

2-4 hrs.*

Approvals:

UL, cUL, NOM

UL, cUL, NOM

UL, cUL, NOM

*Battery Runtime for these models can be increased with the addition of optional external battery packs. Adding external battery packs will also increase recharge time.

All Models: Input Voltage (120V); Input Frequency (60 Hz); Voltage-Regulated Output Voltage Range (120V ±9%); On-Battery Output Voltage Range (120V ± 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B stan- dards); AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G); Compatible Battery Packs (BP48V242U and BP48V603U).

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and

(2) this device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the inter- ference at his own expense.

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.

12

Page 12
Image 12
Tripp Lite 1400VA owner manual SMART1400RM2U SMART1500RMXL2U