Multiple UPS Operation (Parallel) (continued)

Common Battery

In this configuration, a single bank of battery modules is shared by multiple UPS power modules. This not only reduces installation costs, but saves floor space. Note: when using the LCD Screen to set battery charging, divide the charging task equally among all UPS power modules. For example: two UPS power modules are connected to a single bank of battery modules with a 100 amp-hour capacity. To charge the battery bank at a 12 amp charge current rate, select a 6 amp “Battery Charge Current” setting and a 50 amp-hour “Battery Capacity AH” setting individually on each of the LCD Screens of the two UPS power modules. Also note: in a Common Battery configuration, you will not be able to execute a battery test from the LCD Screen.

Start-Up Procedure

This procedure supplies power to and starts up the UPSs. Please check the following items before UPS start-up:

Ensure that all electrical connections to all power modules and battery modules have been completed.

Check that all circuit breakers and isolators are in the off position and battery fuse(s) have been removed.

Ensure that the neutral line and grounding are at the same voltage level.

Apply power to the AC input cables, and check that input voltage, frequency and phase sequence are within the specifications of the UPS and the equipment load.

Check to ensure auxiliary power and fan power (N) fuse isolators are closed.

Using the LCD Display Screen on each UPS power module within the parallel configuration, set the UPS ID. Set a different ID for each power module.

After following all warnings listed in the Safety section and precautions listed above, start-up UPSs according to the following procedure:

NOTE!

Apply each step to each UPS power module within the parallel configuration before moving on to the next step.

Step 1: Install external parallel communication cables between the parallel ports on the UPS power modules to a computer.

Step 2. Turn on (close) the “RESERVE INPUT” Breaker of each UPS power module. The LCD Screen on each UPS power module will display “Bypass Mode”.

Step 3. Turn on (close) the “RECTIFIER INPUT” Breaker of each UPS power module and wait about 30 seconds. The DC BUS voltage will be built up to about 393V DC.

Step 4. Locate the external fuse block(s) on the battery module(s) and turn on (close) the fuses.

Step 5. For each UPS power module individually, simultaneously press the “ON” and “” Buttons and hold for 3 seconds. The inverter will turn on and voltage will build for about 30 seconds. The load will be transferred to the inverter. The LCD Screen will display “Normal Mode”.

Step 6. Measure the voltage on the UPS “OUTPUT” Breaker of each power module to determine if it is normal or abnormal. If the output voltage is normal, turn on (close) the “OUTPUT” Breakers of each power module to supply power to the load. After approximately 30 seconds, the UPS will automatically execute a battery test

13

Page 13
Image 13
Tripp Lite 230/400V, 240/415V AC, 277/480V AC, 220/380V owner manual Start-Up Procedure

220/380V, 277/480V AC, 230/400V, 240/415V AC specifications

Tripp Lite is a renowned manufacturer in the field of power solutions, offering a wide range of products designed to meet various electrical and connectivity requirements. Among its extensive portfolio, Tripp Lite provides effective AC power distribution units (PDUs) that support multiple voltage configurations, including 240/415V AC, 230/400V AC, 277/480V AC, and 220/380V. These PDUs are essential for managing power within industrial, commercial, and data center environments.

One of the main features of Tripp Lite's AC PDUs is their versatility in handling different voltage inputs, which allows them to cater to a wide range of global electrical standards. This feature is crucial for businesses operating in multiple regions or those with diverse electrical equipment that require specific voltage levels. The PDUs are equipped with multiple outlet configurations, ensuring compatibility with various types of plugs used in different countries.

Safety is another critical aspect of Tripp Lite’s design, with built-in protections such as surge protection and circuit breakers. These enhancements help safeguard connected devices from power surges, spikes, and overloads, ultimately reducing the risk of damage and downtime. Additionally, the units are constructed with high-quality materials to ensure durability and reliable performance, even under demanding conditions.

Tripp Lite also integrates advanced technologies into its PDUs to enhance functionality and user experience. Features such as remote monitoring capabilities allow users to track power usage, load balance, and environmental conditions in real time. This data is invaluable for optimizing energy management and ensuring that power distribution is both efficient and effective.

The compact design of Tripp Lite PDUs makes them easy to install in various spaces, including server racks and telecommunications closets. With options for vertical or horizontal mounting, users can customize their setup to best fit their needs. In terms of cooling efficiency, many of these PDUs are designed to facilitate optimal airflow, further enhancing the lifespan of connected equipment.

Tripp Lite’s commitment to delivering high-quality power solutions is evident in their warranty and customer support services. With years of industry experience, Tripp Lite stands out as a reliable partner for businesses looking to enhance their power management systems. The combination of advanced features, robust safety mechanisms, and versatile voltage compatibility makes Tripp Lite PDUs an excellent choice for any organization seeking dependable AC power solutions.