Operation (Special Conditions) (continued)

OPERATION ON OVERLOAD

When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload). If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.

Overload Condition

LCD Display Message

Countdown to Shutdown

 

 

 

102% - 125%

OVERLOAD 102%

1 minute

 

LOAD=XXX% X.XXKW

 

 

 

 

125% - 150%

OVERLOAD 125%

30 seconds

 

LOAD=XXX% X.XXKW

 

 

 

 

>150%

OVERLOAD 150%

2 seconds

 

LOAD=XXX% X.XXKW

 

 

 

 

BATTERY CHARGE WARNINGS

Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.

Battery Charge Warning

LCD Display Message

 

 

Battery charge nearly depleted

BATTERY LOW

 

 

Low battery shutdown

LOW BATTERY! SHUT DOWN…

 

 

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

 

 

Extended Overload (>150%)

OVERLOAD XX%

 

SHUT DOWN…

 

 

Output Short Circuit

SHORT CIRCUIT!

 

SHUT DOWN…

 

 

Remote Shutdown Command

REMOTE

(from DB9 interface)

SHUT DOWN…

 

 

Remote Shutdown Command

EMERGENCY STOP!

(from RJ11 interface)

SHUT DOWN…

 

 

Internal Faults

INVERTER TOO LO

 

SHUT DOWN…

 

 

 

INVERTER TOO HI

 

SHUT DOWN…

 

 

 

DC BUS +/- HIGH/LOW

 

SHUT DOWN…

 

 

 

OVER TEMPERATURE

 

SHUT DOWN…

 

 