Operation (Special Conditions) (continued)

OPERATION OF MANUAL BYPASS SWITCH

Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive filtered AC mains power, but will not receive battery power in the event of a blackout.

SWITCHING UPS TO “BYPASS” MODE

Turn the “ON/OFF” Switch OFF. (LCD will read "ON BYPASS.")

Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.

Turn the AC Input Circuit Breaker OFF.

SWITCHING UPS TO “NORMAL” MODE

Turn the AC Input Circuit Breaker ON.

Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.

Turn the “ON/OFF” Switch ON.

Communications

RS-232 INTERFACE

This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses RS-232 communications to report UPS status and power conditions. Using this port, Tripp Lite software can monitor and manage network power and automatically save open files and shut down equipment during a blackout. Contact Tripp Lite Customer Support at (773) 869- 1234 for information on available SNMP, network management and connectivity software and products.

RS-232 signals and operations include: load level, battery status, battery level, operation mode, AC input voltage, AC output voltage, AC input frequency, temperature inside unit, set shut-down delay time, enable/disable alarm and remote shutdown.

Hardware:

 

Baud Rate:

2400 BPS

Data Length:

8 bits

Stop Bit:

1 bit

Parity:

NONE

Pin assignment:

Pin 2: TXD (Transmit Data)

Pin 3: RXD (Receive Data)

Pin 5: GND (Signal Ground)

12

Page 12
Image 12
Tripp Lite 3-Phase 10kVA Communications, Operation of Manual Bypass Switch, Switching UPS to Bypass Mode, RS-232 Interface