Operation (Normal Conditions) (continued)

TURNING THE UPS OFF

Press the front “OFF” button. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display will show “ON BYPASS.”

Turn the Main Input Switch and Bypass Input Switch Circuit Breakers OFF. Your load will no longer be energized, and the LCD display will be dark.

NOTE: If the UPS System remains off for an extended period of time, it should be turned back on periodically to allow the internal batteries to recharge. The UPS System should be turned on and the internal batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to provide periodic recharge time may cause irreversible battery damage.

SELF-TESTING

When you turn the UPS ON, it will perform a brief self-test. See charts below for display sequences.

Display sequence when AC input power is present:

SELF TESTING...

RECTIFIER OK

CHARGER OK

BATTERY OK

DC TO DC OK

INVERTER TEST

Display sequence when AC input power is absent: (possible only with the "Battery Start" Switch)

SELF TESTING...

BATTERY OK

DC TO DC OK

INVERTER TEST

LCD DISPLAY SELECT BUTTON

Momentarily press the “SELECT” button on the front panel to browse through different power readings on the LCD Display.

BYPASS OUTPUT

R:XXXV R: XXX.XV

S:XXXV S: XXX.XV

T:XXXV T: XXX.XV

(Bypass & Output Voltage)

Press "SELECT" Button

OUTPUT

LOAD

R: XXX%

XXX.XA

S: XXX%

XXX.XA

T: XXX%

XXX.XA

(Output Load & Current)

Press "SELECT" Button

MAINS

INVERTER

R: XXXV

R: XXX.XV

S: XXXV

S: XXX.XV

T: XXXV

T: XXX.XV

(Mains & Inverter Voltage)

Press "SELECT" Button

BYPASS: XX.X Hz

MAINS: XX.X Hz

OUTPUT: XX.X Hz

INVERTER: XX.X Hz

(Bypass, Mains, Output & Inverter Frequency)

Press "SELECT" Button

CHARGE FLOATING

CHARGER: XXX.XV

BATTERY: XXX.XV

BATTERY: XXX.X%

(Charger Mode, Charger/Battery Voltage & Battery Percentage)

Press "SELECT" Button

SN:

XXX

DC BUS:

XXV - XXV

TEMP:

XXX.X˚C

VERSION:

XXX

(Serial Number, DC BUS Voltage, Temperature & Firmware Version)

 

 

 

Press "SELECT" Button

 

 

 

 

 

 

ON:

UPS START

 

 

OFF:

UPS BYPASS

(Button Functions)

 

SEL:

UPS MESSAGE

 

ENT:

SET UPS

 

 

 

 

Press "SELECT" Button

 

 

 

 

 

8

Page 8
Image 8
Tripp Lite 3-Phase 30kVA owner manual Turning the UPS OFF, Self-Testing, LCD Display Select Button

3-Phase 30kVA specifications

The Tripp Lite 3-Phase 30kVA is a robust power protection solution designed for demanding environments, such as data centers, industrial facilities, and large commercial spaces. This uninterruptible power supply (UPS) is engineered to deliver reliable and consistent power while safeguarding sensitive equipment from power fluctuations and outages, making it an ideal choice for businesses that require uninterrupted operations.

One of the main features of the Tripp Lite 3-Phase 30kVA UPS is its ability to provide a high power output of 30,000 VA, which translates to significant flexibility in powering multiple devices and systems simultaneously. This capacity is critical for operations that rely on extensive and mission-critical equipment, ensuring that everything continues to run smoothly even in the event of utility power failure.

The UPS is equipped with advanced technologies designed to enhance its performance. The double-conversion online design ensures that your connected equipment receives clean, stable, and filtered power. This technology isolates sensitive electronics from typical power issues such as surges, sags, and electrical noise, minimizing the risk of damage. Furthermore, the unit features a high-efficiency mode that reduces energy consumption, resulting in lower operating costs and environmental impact.

The Tripp Lite 3-Phase 30kVA UPS also comes with comprehensive monitoring and management capabilities. Its intelligent LCD interface provides real-time information on input/output voltage, battery status, and system configuration, allowing administrators to monitor the UPS easily and make informed decisions regarding power management. Additionally, it supports SNMP compatibility for remote management via a network, enabling IT teams to efficiently oversee power and UPS status from a distance.

Another notable characteristic is the UPS's scalable design, which allows for multiple units to be combined to create a highly efficient power system tailored to the specific needs of the facility. This scalability ensures that the power infrastructure can evolve with growing demands without requiring a complete overhaul.

Overall, the Tripp Lite 3-Phase 30kVA UPS stands out as a reliable, efficient, and user-friendly solution for organizations seeking to enhance their power protection strategy. With its high capacity, advanced technologies, and comprehensive management features, it is well-equipped to support critical operations and ensure business continuity in a world where power integrity is paramount.