Tripp Lite 3-Phase 30kVA Operation Special Conditions, Operation On Bypass-Voltage Out Of Range

Models: 3-Phase 30kVA

1 56
Download 56 pages 63.27 Kb
Page 9
Image 9
Operation (Special Conditions)

Operation (Special Conditions)

OPERATION ON BYPASS—VOLTAGE OUT OF RANGE

While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to nominal.

Bypass Voltage Condition

LCD Display Message

 

 

>15% Higher than Nominal

BYPASS HI NO O/P

 

 

>20% Lower than Nominal

BYPASS LO NO O/P

Was Too High, Now Nominal

BYPASS WAS HI

 

 

Was Too Low, Now Nominal

BYPASS WAS LO

 

 

INVERTER ON WARNINGS

When the inverter is ON, the LCD Display may show any one of the following warnings:

Condition

LCD Display Message

 

 

UPS Output Overload

OVERLOAD 110%

 

 

UPS Charger Failure

CHARGER FAILURE

 

 

Abnormal Input Frequency

FREQUENCY ERROR

 

 

Abnormal Input Phase

PHASE ABNORMAL!

 

 

Battery is Depleting*

ON BATTERY

 

 

Battery Charge is Nearly Depleted*

BATTERY LOW

 

 

* During a prolonged blackout, users should save files and shut down connected equipment.

The “BATTERY LOW” message indicates the UPS's batteries are nearly out of power and UPS shut down is imminent.

OPERATION UNDER SHUTDOWN

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,” “Output” and “Bypass” LEDs will be illuminated.

Condition

LCD Display Message

 

 

Overload Shutdown

ON BYPASS

 

OVERLOAD 150%

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

UPS Output Short Circuit

ON BYPASS

 

SHORT CIRCUIT!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Overtemperature

ON BYPASS

 

HIGH TEMP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Overvoltage

ON BYPASS

 

DC BUS O.V.P.!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

DC BUS Failure

ON BYPASS

 

DC BUS FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

Condition

LCD Display Message

 

 

R/S/T Inverter Output Failure

ON BYPASS

 

R OUTPUT FAIL!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Low Battery

BYPS OFF NO O/P

 

LOW BATTERY!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Remote Shutdown

BYPS OFF NO O/P

 

REMOTE SHUTDOWN

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

Emergency Stop

BYPS OFF NO O/P

 

EMERGENCY STOP!

 

SHUTDOWN...

 

VERSION: XXXXXXX

 

 

9

Page 9
Image 9
Tripp Lite 3-Phase 30kVA Operation Special Conditions, Operation On Bypass-Voltage Out Of Range, Inverter On Warnings