Tripp Lite 3-Phase 30kVA owner manual Specifications continued, Model SU30K3/3INTXR5

Models: 3-Phase 30kVA

1 56
Download 56 pages 63.27 Kb
Page 19
Image 19
Specifications (continued)

Specifications (continued)

Model: SU30K3/3INT

Input

Input Voltage

220/380, 230/400, 240/415V,

 

3ø, 4 Wire (plus ground), wye

Input Frequency

50/60 Hz ± 3 Hz (auto-selectable)

Voltage Correction Range

156-280/270-485V AC

Input Current (Per Phase, On-Line)

45A/43A/41A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>91%

Circuit Breaker

63A (3p)

Input Bypass Circuit Breaker

63A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

User-selectable 220/380, 230/400,

 

240/415V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

50/60 Hz (auto-selectable)

 

(± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Three Packs (20 12V DC Batteries per pack)

Protection

Six UL- or IEC- recognized 30A 600VDC

 

rated cartridge fuses (two per battery pack)

 

and fuse block (1 per battery pack)

Typical Backup Time (Half Load) 13 min. +

Typical Backup Time (Full Load) 5 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

35.3 x 19.3 x 36 in. (89.7 x 49 x 91.4 cm)

Unit Weight

662 lb. (300 kg)

Shipping Dimensions (H xW x D) 43 x 28 x 44.5 in. (109.2 x 71.1 x 113 cm)

Shipping Weight

750 lb. (340 kg)

Model: SU30K3/3INTXR5

Input

Input Voltage

220/380, 230/400, 240/415V AC,

 

3ø, 4 Wire (plus ground), wye

Input Frequency

50/60 Hz ± 3 Hz (auto-selectable)

Voltage Correction Range

156-280/270-485V AC

Input Current (Per Phase, On-Line)

45A/43A/41A

Inrush Current

<300A

Power Factor (Full Load)

>0.95

Efficiency (Full Load/On-Line)

>91%

Circuit Breaker

63A (3p)

Input Bypass Circuit Breaker

63A (3p)

 

 

Output

 

VA

30000

Watts (Power Factor: 0.8)

24000

Waveform (On-Line)

Sinewave

Waveform (On-Battery)

Sinewave

Output Voltage (RMS)

User-selectable 220/380, 230/400,

 

240/415V AC, 3ø, 4 Wire (plus ground), wye

Output Frequency

50/60 Hz (auto-selectable)

 

(± 0.1 Hz on battery)

Voltage Regulation

±2%

Max. Harmonic Distortion

 

(Non-Linear Full Load)

<5%

Overload Capabilities

<102% (continuous), 102%~125% (1 min.),

 

125%~150% (30 sec.), >150% (2 sec.)

Short Circuit Capability

>250A

Crest Factor

3:1

 

 

Battery

 

Battery Type

Sealed, Lead Acid, 240V DC, 9AH

Battery Pack Quantity

Five Packs (20 12V DC Batteries per pack)

Protection

Ten UL- or IEC- recognized 30A 600VDC

 

rated cartridge fuses (two per battery pack)

 

and fuse block (1 per battery pack)

Typical Backup Time (Half Load) 25 min. +

Typical Backup Time (Full Load) 11 min. +

Operation

On-Line Transfer Time

(Line to Battery, Battery to Line) 0 ms

Audible Noise (Full Load @ 1 meter) <65 dBA

Indicators

Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).

Communications

Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.

Connections

Input Terminal Block

100A

Output Terminal Block

100A

 

 

Physical Specifications

 

Unit Dimensions (H x W x D)

48.5 x 19.3 x 36 in. (123.2 x 49 x 91.4 cm)

Unit Weight

935 lb. (424 kg)

Shipping Dimensions (H xW x D) 61.5 x 31 x 44.5 in. (156.2 x 78.7 x 113)

Shipping Weight

1152 lb. (523 kg)

+ Backup times are expandable with additional Battery Packs, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.