![1.2.7 Battery Voltage (LED 5-8)](/images/new-backgrounds/195299/1952999x1.webp)
1. Overview and Features
1.2.7 Battery Voltage (LED 5-8)
LED
Battery Voltage | LED 5 | LED 6 | LED 7 | LED 8 |
25% | On | — | — | — |
50% | On | On | — | — |
75% | On | On | On | — |
|
|
|
|
|
100% | On | On | On | On |
|
|
|
|
|
1.2.8 Voltage Setting (Switch 1-3)*
Switch | ON | OFF |
|
|
|
30 sec (Default) | 5 sec | |
Low Battery Alarm (Switch 2) | 11.2V | 10.9V (Default) |
AC Transfer Voltage (Switch 3) | 190V | 170V (Default) |
* Notes:
1.Switches are located farthest from the battery temperature port. See diagram on page 3.
2.The switches must be set before the system is turned on.
3.Switch 2 sets the low battery voltage alarm level (at higher voltage setting, alarm will sound sooner).
4.Switch 3 sets the
Nominal Voltage | Low Voltage Transfer Point | Return Voltage Point | ||
230V | On | 190 | 200 | |
|
|
| ||
Off | 170 | 180 | ||
| ||||
|
|
|
|
1.2.9 Search Mode Setting (Switch 4)
Search Mode activates when the unit is operating in inverter mode (battery power) to prevent unnecessary battery discharge when electrical power is not required. If the inverter is supporting loads that must constantly be powered, turn off switch 4 to disable Search Mode.
Switch 4 |
|
| Search Mode | Function | ||
|
|
|
|
|
|
|
ON |
|
| Enable | Inverter turns on only if load is >100W | ||
OFF (Default) |
|
| Disable | Inverter always on if AC power is absent | ||
1.2.10 Floating Voltage/Battery Type (Switch 5) |
|
|
| |||
|
|
|
|
|
| |
Switch 5 |
| Floating Voltage | Acceptance Voltage |
| Battery Type | |
ON (Default) |
| 13.8V | 14.5V |
| Absorbed Glass Mat (AGM) | |
OFF |
| 13.2V | 13.8V |
| ||
|
|
|
|
|
|
|
Note: The unit will charge the battery to acceptance voltage, continue for 1 to 12 hours, then drop to floating voltage.
5