200308025 Smart1050-1500SLT Owner’s Manual.qxd 11/14/2003 11:40 AM Page 10

Storage and Service

Storage

First turn your UPS OFF: press the “OFF” switch to turn power off at the outlets, then discon- nect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS bat- teries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period of time, they may suffer permanent loss of capacity.

Service

Before returning your UPS for service, follow these steps:

1.Review the installation and operation instructions in this manual to ensure that the service problem does not originate from a misreading of the instructions. Also, check that the UPS System’s circuit breaker(s) are not tripped. This is the most common cause of service inquiries which can be easily remedied by following the resetting instructions in this manu- al.

2.If the problem continues, do not contact or return the UPS to the dealer. Instead, call Tripp Lite at (773) 869-1233. A service technician will ask for the UPS’s model number, serial number and purchase date and will attempt to correct the problem over the phone.

3.If the problem requires service, the technician will issue you a Returned Material Authorization (RMA) number, which is required for service. If you require packaging, the technician can arrange to send you proper packaging. Securely pack the UPS to avoid damage during shipping. do not use Styrofoam beads for packaging. Any damages (direct, indirect, special, incidental or consequential) to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty. UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the UPS System is within the 2-year warranty period, enclose a copy of your sales receipt. Return the UPS for service using an insured carrier to the address given to you by the Tripp Lite service technician.

Specifications

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.

SmartPro SLT UPS Systems

 

Model:

SMART1050SLT

SMART1500SLT

 

Series #:

AGSM1000DT

AGSM1500DT

 

 

 

 

 

 

Input

 

 

 

Nominal Voltage:*

100, 110, 120 or 127 VAC

100, 110, 120 or 127 VAC

 

Frequency (± 3 Hz.):

60 Hz.

60 Hz.

 

Recommended Dedicated Electrical Circuit:

15 amp

15 amp

 

 

 

 

 

 

Output

 

 

 

Nominal Voltage:*

100, 110, 120 or 127 VAC

100, 110, 120 or 127 VAC

 

Frequency (± 3 Hz.):

60 Hz.

60 Hz.

 

Capacity (VA/Watts)

 

 

 

 

@ 127 VAC:

1050/670

1500/950

 

 

@ 120 VAC:

1050/670

1500/950

 

 

@ 110 VAC:

945/603

1350/855

 

 

@ 100 VAC:

840/536

1200/760

 

Waveform (Line and Battery Modes):

sine wave

sine wave

 

Maximum Harmonic Distortion (Linear Load/Non-Linear Load):

< 3% / < 6%

< 3% / < 6%

 

 

 

 

 

 

Battery

 

 

 

Battery Runtime (Half Load/Full Load) Minutes:

20/7

20/8

 

Battery Recharge Time (to 80% Capacity):

2-4 hours

2-4 hours

 

Transfer Time:

4-8 milliseconds

4-8 milliseconds

 

Battery System Voltage:

36 VDC

36 VDC

 

FCC:

Class B

Class B

 

Approvals:

UL, cUL, NOM

UL, cUL, NOM

 

 

 

 

 

SmartPro XL UPS System

 

Model:

SMART750XL

 

Series #:

AGSM751ST

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

Nominal Voltage:*

100, 110, 120 or 127 VAC

 

 

 

 

 

 

 

 

 

Frequency (± 3 Hz.):

 

 

60 Hz.

 

 

 

 

 

 

 

 

 

Recommended Dedicated Electrical Circuit:

 

 

15 amp

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

Nominal Voltage:*

100, 110, 120 or 127 VAC

 

 

 

 

 

 

 

 

 

Frequency (± 3 Hz.):

 

 

60 Hz.

 

 

 

 

 

 

 

 

 

Capacity (VA/Watts)

 

 

 

 

 

 

 

@ 127 VAC:

750/450

 

 

@ 120 VAC:

750/450

 

 

@ 110 VAC:

675/430

 

 

@ 100 VAC:

600/382

 

Waveform (Line and Battery Modes):

 

sine wave

 

 

 

 

 

 

 

 

Maximum Harmonic Distortion (Linear Load/Non-Linear Load):

< 3% / < 6%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

Battery Runtime (Half Load/Full Load) Minutes:

33/10+

 

 

 

 

 

 

 

 

Battery Recharge Time (to 80% Capacity):

 

2-4 hours

 

 

 

 

 

 

 

 

Transfer Time:

4-8 milliseconds

 

 

 

 

 

 

 

 

Battery System Voltage:

 

 

36 VDC

 

 

 

 

 

 

 

 

FCC:

 

 

Class B

 

 

 

 

 

 

 

 

Approvals:

UL, cUL, NOM

*A set of user-selectable Voltage DIP Switches (see Quick Installation section) match the UPS system's output voltage to the input voltage available at the wall outlet.

+Battery runtime can be extended with the addition of optional Tripp Lite External Battery Packs (sold separately). SMART750XL models use BP36V27 battery packs. External batteries will increase both the battery runtime and the battery recharge time.

10

 

11

Page 7
Image 7
Tripp Lite 1500SLT, Smart1050 owner manual SmartPro SLT UPS Systems, SmartPro XL UPS System