7. Electrical Connections
WARNING! This configuration is for hardwire installations only/ Do not change this setting when using the supplied
1From the HOME screen, scroll right to the SETUP screen and unlock the SETUP menus. To unlock SETUP menus, press ENT > Open Password > enter your password > SET. The default password is 000000.
|
|
| | |
| |
| | |
| | | ||
|
|
| | |
2Press the HOME button.
3Scroll right to the SETUP screen and scroll down to the following menu:
4Press ENT to access the TECHNICIAN MENU.
Note: An informational screen will be displayed first.
5Press SET to continue.
6Press SET to continue to highlight the current limit. Using the up, down, left and right arrows, set the current to 30.0 Amps. Press ENT when done. Press HOME button to exit.
WARNING! Do not place setting at any value other than 24.0 Amps (with input Cord) or 30.0 Amps (Hardwire). WARNING! The SRXCOOL33K is
8. Network Card Connections
The SRCOOL33K/SRXCOOL33K can be remotely monitored and controlled via SNMP, Web, telnet or Modbus. The unit comes with a Modbus card
Remote monitoring and control via SNMP, Web or telnet requires a network card such as Tripp Lite’s SNMPWEBCARD. In order to install a
To install a
1 Remove the front panel and locate the Modbus card slot A .
2 Remove the screws holding the card in place and gently slide the card out of the slot.
3 Align and insert the
Note: Please review and follow all of your network card’s installation and configuration documents before installing into the SRCOOL33K/ SRXCOOL33K.