Communications (continued)

RS-232 Port/Ethernet Port/SNMP Card Slot

The RS-232 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite power management software. The RS-232 port uses RS-232 communications to report UPS status and power conditions. Contact Tripp Lite Customer Support for information on available SNMP, network management and connectivity software and products.

The Ethernet Port is an RS-232 port that accepts an optional RS-232/RJ45 Ethernet Adapter (sold separately).

The SNMP Card Slot accepts an optional internal SNMP/Web card. Contact Tripp Lite Customer Support for information on available SNMP, network management and connectivity software and products.

Ethernet Power

The Ethernet Power connection provides 12VDC power to the optional adapter.

Generator Contact

This port connects to an auxiliary power generator. When the generator is operating to support the equipment load, the UPS System will automatically reduce its charge current by 50% in order to prevent overloading of the generator.

GENERATOR CONTACT

G-ON'

GND

GENERATOR

CONTACT (Normally Open)

21

Page 21
Image 21
Tripp Lite SU80K3/3INTPM, SU80K3/3PM RS-232 Port/Ethernet Port/SNMP Card Slot, Ethernet Power, Generator Contact