NOTE

Keep in mind that the door of the unit may be mounted on either side of the cabinet (see REVERSING THE DOOR). All U-Line units have a zero clear- ance for the door to open when the handle is on the right (see Figure 1).

Additional clearance is need- ed for Combo Models 29A, 29FF, 75A, and 75FF only, when the door handle is on the left. See BUILT-IN INSTAL- LATION for additional clear- ance requirements for these models.

CABINET

OR WALL

DOOR

SWING

0"

CLEARANCE

NEEDED

UL124

Figure 1

3.On Ice Maker models SP18, BI-15, BI-95, BI-98 and Combo Series 29 and 75, install a 1/4 inch copper water line (not supplied with unit) from the nearest COLD water pipe. When connecting the water supply, follow these guidelines:

Review the local plumbing codes before you install the unit.

In most instances, the cold water supply will come from the basement through a hole in the floor.

The water pressure should be between 15 and 150 psi.

Install a shut-off valve in the 1/4 inch supply line.

Connect sufficient tubing to the unit to allow the unit to be moved for cleaning and servicing. However, make certain that the tubing is not pinched or damaged during installation.

U-Line recommends the use of copper tubing for installation.

4.Position the unit to allow free air flow through the front grill

(see Figure 2).

5. Wipe out inside of unit and ice

bucket with a damp cloth.

UL005A

Figure 2

5

Page 7
Image 7
U-Line ICE-MAKER/REFRIGERATOR user manual Cabinet Or Wall Door Swing Clearance Needed