United States Stove VF30IN, VF30IL manual Ventilation Air, Air For Combustion And Ventilation

Models: VF30IL VF30IN

1 28
Download 28 pages 60.47 Kb
Page 10
Image 10
VENTILATION AIR

AIR FOR COMBUSTION AND VENTILATION

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 11.

C.Install a lower BTU/Hr firebox, if lower BTU/Hr size makes room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING

If the area in which the firebox and gas log heater may be operated is smaller than that defined as an unconfined space, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an ad- joining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor into adjoining room ( see options in Figure 1).

Follow the National Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING

Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

FIGURE 1. Ventilation Air from Inside Building

10

Page 10
Image 10
United States Stove VF30IN, VF30IL manual Air For Combustion And Ventilation, Ventilation Air from Inside Building