CONFIGURATION
INSTALLER
CONFIGURATION
The configuration settings can be changed at any time to meet system or personal requirements.
Press PROGRAM RUN to make certain the thermostat is in the run program mode, then press TIME
FWD and TIME BACK at the same time to enter the configuration menu. The display will change to show the first option on the configuration menu. The chart on page 16 briefly describes each option on the menu. Following are more detailed descriptions of the options recommended for selection by the installer. For more detailed descriptions of other options, refer to the Operating Instructions. Make
selections for each option as required.
When the option is set to your choice, press TIME FWD to change the display to the next step. To return to a previous option, press
TIME BACK .
To exit the configuration menu at any time, press PROGRAM .
SELECTABLE ENERGY MANAGEMENT RECOVERY
Energy Management Recovery (EMR) causes the thermostat to start operating the system early in order to make the building temperature reach the programmed setpoint at the programmed time. In heating, the thermostat will start 5 minutes early for every °F difference between the room temperature and
the next programmed temperature. In cooling the thermostat uses 15 minutes per °F.
The maximum time the thermostat can start early in heating is 75 minutes. The maximum time the thermostat can start early in cooling is 3 hours and 45 minutes. Cooling can start earlier because it takes longer to reach temperature.
ADJUSTABLE
ANTICIPATION
This option allows the cycle times in heating and cooling to be increased or decreased. The factory set values can be adjusted higher for longer cycles or lower for shorter cycles.
The adjustment range for HEATING is from 2 to 40. The factory preset is 5. The adjustment range for