Vermont Castings Intrepid
B
A
Fig. 10 Minimum clearances.
Connecting Flue Pipe - Clearances
Single wall connecting fluepipes can reach extremely high temperatures; therefore, clearances from the con- necting fluepipe (chimney connector) must comply with the requirements of Part J of Building Regulations 2000 (Combustion Appliances and Fuel Storage Systems). This can be achieved by following the recommenda- tions of Approved Document ‘J’. These are as shown in Figure 11.
ST486a
at least |
|
3 x D | D |
|
at | leastD |
x | |
| 3 |
at least 1.5 x D
at least 3 x D
Fluepipe
D |
| at least | |||
| 1.5 x D | ||||
|
|
|
|
|
|
|
|
|
|
|
|
at least 1.5 x D
at least 1.5 x D
at least 1.5 x D
Elevation
Without
Shield
Fig. 11 Connecting fluepipe clearances.
| Air space of at least 12 mm |
Plan Without | between noncombustible shield |
Shield | and combustible material |
| Plan With |
Elevation | Shield |
With Shield | ST911 |
|
10 | 2000970 |