Vermont Castings Intrepid
Flexible Con- |
nector |
Mantel Shield |
Fireplace Adap- |
tor Kit |
ST245 |
Fig. 7 Chimney connector enters chimney through the fire- place opening.
Wall Pass-Throughs
Whenever possible, design your installation so that the connector does not pass through a combustible wall. If you are considering a wall
Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall
Always adhere to local building codes when installing a wall
All combustible material in the wall must be removed around the
Figure 9 shows an alternate method in which all com- bustible material in the wall is cut away to provide the required clearance that is three times the pipe diameter. The resulting space must remain empty. A
8
NOTE: Do not vent your Intrepid
DO NOT CONNECT AN INTREPID
Wall Stud
Chimney |
|
|
Connector |
|
|
IN |
|
|
TR |
| |
| EPI |
|
| D II |
|
| 12” of |
|
| Noncombustible | |
| Material |
|
Floor Protec- |
|
|
tion |
| ST493a |
|
| |
Fig. 8 An approved wall | ||
18” (460mm) clearance all |
| |
around the pipe |
| |
| Flush Mounted |
|
| Sheet Metal |
|
| Cover |
|
|
| ST494a |
Fig. 9 An approved wall |
| |
|
| 2000970 |