NV360/580 Series

Troubleshooting

SIT NOVA 820 MILLIVOLT VALVE

NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the "ON" position.

WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.

 

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

1.

Spark ignitor will not light.

A. Defective or misaligned elec-

Using a match, light pilot. If pilot lights, turn off pilot and

 

 

 

trode at pilot.

push the red button again. If pilot will not light - check gap

 

 

 

 

at electrode and pilot -should be 1/8" to have a strong

 

 

 

 

spark.

 

 

 

B. Defective ignitor (push button)

Push piezo ignitor button. Check for spark at electrode

 

 

 

 

and pilot. If no spark to pilot, and electrode wire is prop-

 

 

 

 

erly connected, replace ignitor.

2. Pilot will not stay lit after

A. Defective pilot generator (ther-

Check pilot flame. Must impinge on thermocouple/ther-

 

carefully following lighting

mocouple), remote wall switch.

mopile. NOTE: This pilot burner assembly utilizes both - a

 

instructions.

 

thermocouple and a thermopile. The thermocouple oper-

 

 

 

 

ates the main valve operation ("ON" and "OFF"). Clean

 

 

 

 

and/or adjust maximum flame impingement on thermopile

 

 

 

 

and thermocouple.

 

 

 

B. Defective automatic valve.

Turn valve knob to "PILOT". Maintain flow to pilot; millivolt

 

 

 

 

meter should read greater than 10 mV. If the reading

 

 

 

 

is okay and the pilot does not stay on, replace the gas

 

 

 

 

valve. NOTE: An interrupter block (not supplied) must be

 

 

 

 

used to conduct this test.

3. Pilot burning, no gas to

A. Wall switch or wires defective.

Check wall switch and wires for proper connections.

 

main burner.

 

Jumper wire across terminals at wall switch, if burner

 

 

 

 

comes on, replace defective wall switch. If okay, jumper

 

 

 

 

wires across wall switch wires at valve. If burner comes

 

 

 

 

on, wires are faulty or connections are bad.

 

 

 

B. Thermopile may not be gener-

1. Be sure wire connections from thermopile at gas valve

 

 

 

ating sufficient millivoltage.

terminals are tight and thermopile is fully inserted into

 

 

 

 

pilot bracket.

 

 

 

 

2. One of the wall switch wires may be grounded.

 

 

 

 

Remove wall switch wires form valve terminals if pilot

 

 

 

 

now stays lit, trace wall switch wiring for ground. May

 

 

 

 

be grounded to fireplace or gas supply.

 

 

 

 

3. Check thermopile with millivolt meter. Take reading at

 

 

 

 

thermopile terminals of gas valve. Should read 250-

 

 

 

 

300 millivolts (minimum 150) while holding valve knob

 

 

 

 

depressed in pilot position and wall switch "OFF".

 

 

 

 

Replace faulty thermopile if reading is below specified

 

 

 

 

minimum.

 

 

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

 

 

D. Defective automatic valve op-

Turn valve knob to "ON", place wall switch to "ON". Milli-

 

 

 

erator.

volt meter should read greater than 100 mV. If the reading

 

 

 

 

is okay and the burner does not come on, replace the gas

 

 

 

 

valve.

4.

Frequent pilot outage

A. Pilot flame may be too low or

Clean and/or adjust pilot flame for maximum flame im-

 

problem.

blowing (high) causing the pilot

pingement on thermopile and thermocouple.

 

 

 

safety to drop out.

 

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the flue

 

 

 

terminal.

gases).

 

 

 

 

 

20003565

17

Page 17
Image 17
Vermont Casting NV580, NV360 manual Thermocouple