NVB Series
EB-1 Electrical Box
The fireplace, when installed, must be elec- trically connected and grounded in accor- dance with local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code.
For USA installations, follow local codes and the National Electrical Code, ANSI/ NFPA No. 70.
It is strongly suggested that the wiring of the
Ensure that the power to the supply line has been disconnected before commenc- ing this procedure.
Once the fireplace is secured, complete wiring the fan kit. Remove knockout in the center of the back of the EB1 and install listed cable clamps. Feed electri- cal wire through cable clamp leaving approximately six
(6)inches of wire exposed through the EB1. Secure cable clamp to the wire.
Attach white wire from power source to one (1) wire of receptacle and secure with a nut. Attach black wire from power source to the other wire of the receptacle and secure with a nut. Be sure nuts are tightened securely.
Secure the EB1 assembly to the inside of the electrical box coverplate using two (2) screws. Attach the cover to the face of the EB1 while being careful to position excess wire completely within the EB1. Attach the cov- erplate to the fireplace. (Fig. 11)
Inside
Electrical Box
�������������
Outside
Front | Of | Unit |
| ||
| FP580 | |
|
|
Fig. 11 Junction box
Install the Venting System,
Flashing and Termination
See venting installation instructions provided by the B- Vent manufacturer.
Refer to Pages
•Minimum vertical chimney height — 12 feet (3.65 m).
•Maximum vertical height — 40 feet (12 m).
•Minimum height with two 90° elbows — 16 feet (4.06m)
•Elbow requirements allow a maximum of two 90° elbows or four 45 degree elbows per installation. (Two 45 degree elbows = One 90° elbow.) See venting chart for proper elbow offset runs. Use Table 4 for NVB36/42 installations when not in- stalling the GSKBB Single Panel Glass Door. Use Table 5 for NVB36/42 installations when install- ing the GSKBB Single Panel Glass Door.
For firestop positioning, refer to Figure 12. Only one
(1)firestop required per frame. NOTE: A firestop is not required at the roof.
Attic Installation
Firestop position when area above ceilign is an attic. Nails (4)
Firestop Spacer
Joist
Ceiling Installation
Firestop position when are above ceiling is NOT an attic.
(Firestop/draftstop appearances may vary. Only one (1) firestop required per frame.)
FP384
Fig. 12 Firestop/draftstop positions.
10 | 7412950 |