Instructions for RF Comfort Control Valve

Instructions for RF Comfort Control Valve

SDDVTC Series

The Comfort Control valve allows remote control of tem- perature, fan and flame appearance.

NOTE: The antenna should hang in free air away form grounded metal.

Operation

1.

If the manual switch is in remote position, switch it to

 

LOCAL. (Fig. 56)

2.

Turn the pilotstat knob counterclockwise from OFF to

 

the PILOT position, push the knob down, and hold in

 

position. The pilot valve opens and allows gas to flow

 

to the pilot burner.

3.

Push plunger on the piezo until the pilot burner is lit.

 

When the pilot burner is lit, the LED on the control

Stardance Direct Vent/Natural Vent Gas Heater

7.If the manual switch is in the LOCAL position, the valve will be at the highest fixed pressure setting and the fan will be at the highest fixed speed. The trans- mitter will control the fan only.

Shut Off Procedure

If the manual switch is in the REMOTE position, the transmitter can shut off the main burner and fan. How- ever, the control is still on and a command from the transmitter can turn on the main burner or fan.

To shut off the system, turn the pilotstat knob clockwise to the OFF position. This action closes the main gas and safety valves. The transmitter cannot turn on the main burner or fan.

Transmitter Operation

Off Mode

will come on after approximately 40 seconds and

will provide 1 short blink continuously in the normal

mode. When the light turns off which will be approxi-

mately 10 seconds after it has been continuously

red, the receiver/valve is fully powered.

Motor Top Cap

Piezo Ignitor

 

 

 

 

 

 

 

 

 

 

PILOT

OFF

 

ON•

 

Mode

Auto

On

Off

Countdown

Timer

Fan Operation

FP1039

Display

Room Temperature

Set Temperature

Flame Height Level

Fan Speed Level

Countdown Timer

Low Battery

Flame

Up

Increase Flame Height,

Fan Speed Timer, or

Set Point

Shut Off Procedure Down

Decrease Flame, Fan

Speed Timer or Set

Point

LOCAL

REMOTE

LED

 

 

 

LED

Local/Remote

Pilotstat

Plug

Switch

Knob

 

Antenna FP1037

Fig. 56 Comfort control valve.

4.Release the knob. The shaft will move upward. The pilot burner should now stay burning. If the pilot burner goes out, repeat step 2.

5.Turn the knob counterclockwise to the ON position. If the manual switch is in the LOCAL position, the main burner will turn on immediately.

6.ON the initial use of a transmitter, a recognition operation is required between the receiver/valve and transmitter. Change the switch from LOCAL to RE- MOTE. Press the fan or flame button on the transmit- ter within 30 seconds. The LED will blink indicating the transmitter will now work with the receiver/valve. If the switch continues in the REMOTE position, the transmitter will now control the main valve, flame modulation level and fan control.

Fig. 57 Transmitter diagram.

In the OFF mode, the fireplace flame and fan are off, the display will show OFF and displays the room temperature. If the receiver is in REMOTE mode, the fireplace will shut off.

On (Manual) Mode

In the ON mode, the room temperature, flame and fan levels will be shown. MANUAL will appear next to both the flame and fan icons.

When the control is in the ON mode, the flame and fan levels, and delay timer are changed with the up and down buttons. To change the flame level, press the flame button followed by an arrow key. To change the fan level, press the fan key followed by an arrow key. Pushing the arrow key once will change the level by one unit.

Delay Timer Mode

The shut off delay timer has a maximum of 2 hours and a minimum of zero minutes. To change the timer level, press the time key followed by an arrow key. Pushing the key once will change the timer by 10 minutes.

20012734