Stardance Direct Vent/Natural Vent Gas Heater

Installation Requirements

Requirements for the Commonwealth of Massachusetts

All gas fitting and installation of this heater shall only be done by a licensed gas fitter or licensed plumber.

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW, KEEP

CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

4

20012734

Page 4
Image 4
Vermont Casting SDDVT manual Installation Requirements, Gas Equipment Venting System not Provided

SDDVT specifications

Vermont Casting's SDDVT, or the Signature Series Direct Vent Technology, represents a remarkable blend of design, efficiency, and functionality in the world of high-performance heating appliances. Known for its commitment to craftsmanship, Vermont Casting has long been synonymous with quality, and the SDDVT is no exception.

One of the standout features of the SDDVT is its advanced direct venting capability. This system allows for efficient venting of combustion gases directly outside, minimizing the risk of backdrafting and ensuring optimal indoor air quality. It draws air from the outside for combustion, creating a more controlled environment that enhances both efficiency and safety. Homeowners can rest easy knowing that the SDDVT provides a reliable heating solution while protecting indoor air quality.

Another significant aspect of the SDDVT is its high-efficiency performance. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating, the SDDVT maximizes heat output while minimizing fuel consumption. This efficiency translates to lower energy bills and a reduced carbon footprint, making it an environmentally friendly choice for heating. The unit is designed to operate effectively even in extremely cold temperatures, ensuring comfort throughout the winter months.

The SDDVT also boasts an array of customizable options that appeal to a wide range of aesthetic preferences. Available in various finishes and styles, including traditional cast iron and sleek modern designs, homeowners can select a model that complements their decor. The unit features a large viewing glass that provides an unobstructed view of the flames, creating a cozy ambiance that enhances the living space.

Incorporating cutting-edge technology, the SDDVT includes electronic ignition and advanced control systems, allowing users to easily manage their heating preferences. The integration of smart technology enables compatibility with home automation systems, giving users added convenience and control.

Overall, Vermont Casting's SDDVT is an exemplary heating solution characterized by its innovative direct venting technology, high efficiency, and customizable design options. With a focus on quality and performance, this unit exemplifies the brand's dedication to providing sustainable and effective heating solutions tailored to modern living. Whether for new construction or retrofitting existing spaces, the SDDVT stands as a premier choice for comfort and style.