GAS CONNECTION

GAS CONNECTION

GAS DATA

Model

INPUT BTU/HR

MANIFOLD PRESSURE

 

 

 

 

Natural

Propane

Natural

Propane

 

GCO2D, GCO2C

25,000

25,000

3.5" w.c. (0.8 kPa)

10" w.c. (2.5 kPa)

 

 

 

 

 

Gas supply connections and any pipe joint compound must be resistant to the action of propane gases.

The oven is provided with a regulator integral to the gas solenoid valve, and requires no regulator external to the device.

A gas shutoff valve is supplied with each oven and is located at the bottom of the control panel. No tools are required to access this valve.

Connect the oven(s) to the gas line after leveling. The gas supply line must be at least the equivalent of 3/4" (1.9 cm) iron pipe. Make sure the pipes are clean and free of obstructions, dirt and piping compound.

TESTING THE GAS SUPPLY SYSTEM Prior to lighting, check all joints in the gas supply for leaks. Use soap and water solution. Do not use an open flame.

A.Check all joints prior to the gas valve (solenoid) before lighting unit.

B.Check all joints beyond gas valve (solenoid) after unit is lit.

TESTING THE GAS SUPPLY SYSTEM

The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures greater than 1/2 psig (3.45 kPa).

The oven must be isolated from the gas supply piping system by closing the manual shutoff valve during pressure testing of the gas supply system at test pressures equal to or less than 1/2 psig (3.45 kPa).

GAS PRESSURES AND ORIFICES

Natural Gas

The burner orifices are sized to deliver the nameplate input rating (25,000 BTU/hr) at a gas manifold pressure of 3.5" w.c. (water column) (0.8 kPa). The gas pressure regulator is integral to the gas solenoid valve, and is factory set to supply 3.5" w.c. (0.8 kPa) as required for natural gas.

Propane Gas

The burner orifices are sized to deliver the nameplate input rating (25,000 BTU/hr) at a gas manifold pressure of 10.0" w.c. (water column) (2.5 kPa). The gas pressure regulator is integral to the gas solenoid valve, and is factory set to supply 10.0" w.c. (2.5 kPa) as required for propane gas.

BURNER AIR SHUTTER ADJUSTMENTS

The burner has fixed, factory adjusted air openings and requires no field adjustment.