C24GA SERIES GAS CONVECTION STEAMERS

Gas Connection Data

FLEXIBLE GAS CONNECTORS BTU/hr. FLOW CAPACITY 1, 2

 

 

LENGTH 3

 

 

LENGTH 3

 

 

End Fittings - (1) Quick Disconnect

End Fittings - Both Threaded

 

 

& (1) Threaded

 

 

 

 

 

ID

36"

48"

60"

72"

36"

48"

60"

72"

½"

77,000

68,000

60,000

55,000

120,000

106,000

93,000

86,000

¾"

218,000

180,000

158,000

139,000

256,000

225,000

198,000

175,000

1"

379,000

334,000

294,000

279,000

512,000

451,000

397,000

350,000

1¼"

615,000

541,000

476,000

419,000

946,000

833,000

733,000

645,000

1.Flow rating BTU/hr. 0.64 SP. GR @ 0.5 inch W.C. pressure drop.

2.BTU/hr. flow capacities are based on Dormont Mfg. Co. Supr-Safe gas line connectors and are provided for reference. Additional quick disconnect fittings, swivels, or manual shut off valves will reduce the BTU/hr. flow capacities listed in this table. If other flexible gas connectors are used, check the manufacturer’s specifications for BTU/hr. flow capacities. Supr-Safe is a registered trademark of the Dormont Manufacturing Company.

3.The maximum length for a flexible gas connector is 72" per National Fuel Code standards.

BLACK IRON PIPE BTU/hr. FLOW CAPACITY 1, 2, 3

Natural Gas

 

Nominal Inside Diameter of Pipe

 

 

Pipe Length

½"

¾"

1"

1¼"

1½"

2"

15'

76,000

172,000

345,000

750,000

1,220,000

2,480,000

30'

52,000

120,000

241,000

535,000

850,000

1,780,000

45'

43,000

99,000

199,000

435,000

700,000

1,475,000

60'

38,000

86,000

173,000

380,000

610,000

1,290,000

75'

 

77,000

155,000

345,000

545,000

1,120,000

90'

 

70,000

141,000

310,000

490,000

1,000,000

1.Flow rating BTU/hr. 0.64 SP. GR @ 0.3 inch W.C. pressure drop.

2.BTU/hr. flow capacities are based on Schedule 40 pipe, include a tolerance for pressure losses in gas piping systems are provided for reference.

3.Count each 90° elbow as 3' of gas pipe for the purpose of calculating total pipe length.

— 8 —

Page 8
Image 8
Vulcan-Hart ML-136057, ML-136056 operation manual Length, End Fittings 1 Quick Disconnect End Fittings Both Threaded