MATERIALS

INSTALLATION

5)Pull the vent connector plate through the tapered brackets and fasten to the front plate. See page 9.

6)Slide the unit fully into the fireplace and level.

7)Test gas pressure, page 11. Check aera- tion, page 12.

8)Assemble and install the shroud. See page 12.

9)Install Optional Door Grill. See page 13.

10)Install the log set. See page 13.

11)Install Optional Remote Control, and Op- tional Wall Thermostat, if required. See pages 13 and 14.

12)Explain controls to the homeowner.

15)Final check: Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly. This in- cludes:

a)Clocking the appliance to ensure the correct firing rate.

b)Adjusting the primary air, if required, to ensure that the flame does not carbon. See page 12.

c)Ensuring that the appliance is venting correctly.

MATERIALS

REQUIRED

WARNING:

Electrical Grounding Instructions This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.

CLEARANCES TO COMBUSTIBLES

The following clearances to combustibles must be observed:

 

From Unit

Sides

A 9" / 229 mm

Unit to Unprotected Mantel

B

16" / 406 mm

Unit to Protected Mantel*

B

12" / 305mm

*Mantel shield must have a 1" (25mm) air space between the mantel and shield and a 1" (25mm) gap between on the back of the shield and the facing.

In addition to these clearances, adequate ac- cessibility clearance for servicing and proper operation must be maintained.

Do not in any way obstruct the air inlets that are located on the front of the heater.

Combustible Mantels are permitted within the shaded area.

When the Insert is installed in a fireplace that is elevated 5" or higher, no floor protection is required in front of the appliance.

No electrical power supply is required for the gas control to operate. A 120 Volt AC power cord is hooked up to the fan switch and blower. Plug 3 wire cord into a suitable receptacle. Do not cut the ground terminal off under any circumstances.

When connected with 120 volts, the appliance must be electrically grounded in accordance with local codes, with a current version of CSA C22.1 (in Canada) or in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70-1987.

Note: This unit is equipped with a heat sensor thermodisc which will prevent the blower from operat- ing until the unit reaches the cor- rect temperature.

Floor Protection

An approved floor protector is required con- sisting of a layer of 1/2" (13mm) Wonderboard (or Durock or equivalent) that extends 9" (229mm) in front of the fireplace measured at the base (this equals 16" from the fireplace opening), and as wide as the appliance.

Note: If the appliance is installed in a fireplace that is elevated 5" (127mm) or higher (i.e., a Water- ford Zero Clearance Cabinet, zero clearance fireplace, brick plinth, etc.), no floor protection is re- quired in front of the appliance.

Combustibles are permitted within the shaded area, on either side.

Waterford E61 Gas Fireplace Insert

7