THIMBLES
Thimbles for chimneys or vent connectors should be of fire clay (ASTM C 315, specifications for Clay Flue Linings), galvanised steel of minimum thick- ness of 24 gauge, or material of equivalent durabili- ty. Thimbles should be installed without damage at the liner. The thimble should extend through the wall to, but not beyond, the inner face of the liner and should be firmly cemented to masonry.
Thimbles should be located to provide adequate pitch or rise of chimney or vent connectors and, where the ceiling above the appliance is constructed of combustible material, the location of the thimble should provide minimum clearance required for the connector as specified in section under Minimum Clearances.
Insulation material used as part of wall
CHIMNEY CONNECTOR SYSTEMS, THIMBLES, AND CLEARANCES FROM COMBUSTIBLE WALLS
1.Minimum 3 1/2” (90mm) thick brick masonry wall framed into combustible wall with a min. of 12” (305mm) brick separation from clay liner to combustibles. Fire clay liner (ASTM C315 or equivalent) min. 5/8” (16mm) wall thickness, should run from outer surface of brick wall to, but not beyond, the inner sur- face of chimney flue liner and should be firmly cemented in place.
Minimum chimney clearance to brick and combustibles 2” (50mm)
Minimum clearance 12” (300mm) of brick
Fire Clay Liner
Chimney connector
Minimum 12” (300mm) to combustibles
Masonry
Chimney
FIGURE A constructed to
NFPA 211
2.Solid insulated listed
length shall not penetrate the chimney liner.
Minimum chimney clearance from masonry to sheet steel supports and combustibles 2” (50mm)
(230mm) |
|
|
|
| |||
|
| ||
|
| refractory | |
|
| cement | |
|
|
|
|
|
|
| |
|
| Chimney |
|
| |||
|
| length flush |
|
|
| with inside |
|
|
| of flue |
|
|
|
|
|
Masonry chimney constructed to NFPA 211
Factory built chimney length
Air space 9” (230mm) minimum
FIGURE B
3.Sheet steel chimney connector, min. 24 gauge in thickness, with a ventilated thimble, min. 24 gauge in thickness, having two 1” (25mm) air channels, separated from com- bustibles by a min. of 6” (150mm) of glass fibre insulation. Opening should be covered and thimble supported with a sheet steel support, min. 24 gauge in thickness. Supports should be securely fastened to wall surfaces on all sides and should be sized to fit and hold chimney section. Fasteners used to secure chimney sections should not penetrate chimney flue liner.
Minimum chimney clearance to sheet steel supports and combustibles 2” (50mm)
Two air channels each 1” (25mm)
Chimney connector
Minimum 6” (150mm) glass fibre insulation
Sheet steel | Two ventilated air | |
supports | ||
channels each 1” | ||
| ||
| (25mm) constructed | |
| of sheet steel |
FIGURE C
4.Solid insulated listed
8