Waterford Appliances LEPRECHAUN 90 O.S.A Outside Air Connection, Mobile Home Installation

Models: LEPRECHAUN 90 O.S.A

1 12
Download 12 pages 24.12 Kb
Page 4
Image 4
OUTSIDE AIR CONNECTION

WARNING

DO NOT OBSTRUCT FREE AIR SUPPLY TO THE AIR INLET DUCT LOCATED AT THE BACK OF THE STOVE.

DO NOT CONNECT TO OR USE IN CONJUNC- TION WITH ANYAIR DISTRIBUTION DUCTWORK UNLESS SPECIFICALLY APPROVED FOR SUCH INSTALLATIONS.

OUTSIDE AIR CONNECTION

This stove may be connected direct to the outside of the house for its combustion air supply.

Note: It is recommended to use the shortest possible outside air supply ducts. Supply ducts with long runs, multi bends and corners may reduce air volume supply due to excessive drag.

When connecting this stove to an outside air supply the optional outside air kit must be used, which includes a spigot, wire mesh, and fixing screws.

a.Fit the cast iron spigot into the air inlet (Part No. 39).

b.Connect a 4” (100mm) stainless steel, gal vanised ridge or flexible pipe to the air inlet spigot.

c.Fit a 4” (100mm) stainless steel or gal- vanised sweep bend to the outside of the air supply pipe.

d.Fit the stainless mesh to the downturn of the bend terminus using the fixing screws sup plied with the outside air kit.

e.Make sure that all joints are secured using the fixing screws supplied with the outside air kit.

f.The outside air terminus must be fitted with the 1/4” (6mm) x 1/4” (6mm) stainless wire mesh to prevent leaves and rodents entering from the out side.

g.Air inlets traversing cavity walls should include a continuous duct across the cavity. The duct should be installed in such a man ner as not to impair the weather resistance of the cavity.

h.Joints between air vents and outside walls should be sealed to prevent ingress of mois

ture.

l.This stove is listed for Mobile home installa tion provided it is properly connected to an outside air supply and a listed chimney with a ceiling support and spark arrester.

MOBILE HOME INSTALLATION

In addition to standard installation instructions the following requirements are mandatory for installation in a Mobile Home.

CAUTION: Do not obstruct combustion air opening.

1.The stove must be permanently bolted to the floor of the Mobile Home using the floor screws provided.

2.The stove must have a permanent outside air source for combustion.

3.The stove must be grounded to the steel chassis of the Mobile Home.

4.A listed chimney system, roof thimble, spark arrestor and roof flashing kit suitable for use in Mobile Homes must be used.

5.If the chimney exits the Mobile Home at a location other than through the roof, and exits at a point 7ft. (2100mm) or less above the ground level on which the Mobile Home is positioned, a guard or method of enclosing the chimney shall be fitted at the point of exit for a height up to 7 ft.(2100mm).

6.The chimney shall be attached directly to the room heater and shall extend at least 3 ft. (910mm) above the part of the roof through which it passes. The top of the chimney should project at least 2 ft. (610mm) above the highest elevation of any part of the Mobile Home within 10 ft. (3050mm) of the chimney.

4

Page 4
Image 4
Waterford Appliances LEPRECHAUN 90 O.S.A operating instructions Outside Air Connection, Mobile Home Installation