Watlow Electric user manual RUI/Gateway & Modbus TCP Configuration & Programming Example, each

Models: RUI/Gateway

1 20
Download 20 pages 7.64 Kb
Page 13
Image 13
each:

RUI/Gateway & Modbus® TCP

Configuration & Programming Example

Using KEPServerEX 4.0

each:

PV1 of PM1 = 400361 (offset = 0) PV1 of PM2 = 405361 (offset = 5000) PV1 of PM3 = 410361 (offset = 10000) PV1 of PM4 = 415361 (offset = 15000)

29.Now that we know the finer details of the Modbus® offset prompts lets go back to KEPServerEX and look closer at the tag configuration and properties.

As can be seen above the “Tag Properties” dialogue box will open after clicking on the blue link identified as (“Click to add…”). The name and description are user defined where the Modbus® address will be specific as it relates to the member being read or written to.