Watlow Electric user manual RUI/Gateway & Modbus TCP, Configuration & Programming Example

Models: RUI/Gateway

1 20
Download 20 pages 7.64 Kb
Page 2
Image 2
RUI/Gateway & Modbus® TCP

 

 

 

 

 

RUI/Gateway & Modbus® TCP

 

 

 

 

 

Configuration & Programming Example

 

 

 

 

 

 

Using KEPServerEX 4.0

 

3.

Some notables regarding the graphic above. In the steps that follow we are going to focus on

 

four of the prompts shown: a. Modbus® Enable (Mb;E) b. Gateway instance (GTW)

 

c. Gateway enable (du;En) d. Modbus® offset (M;oF)

 

4.

Notice in the graphic in step 2 that the RUI/Gateway has 2 “Com” instances. Com instance 1

 

will always be Standard Bus and Com instance 2 will always be the user protocol of choice, in

 

this case, Modbus® TCP. This protocol when ordered also comes standard with EtherNet/IPTM

 

(Industrial Protocol) as well. When setting the prompts for Com instance 2 you must first

 

enable Modbus® TCP, EtherNet/IPTM or both. For the purpose of this paper the prompt

 

displayed as Mb;E will be set to yes (Modbus® TCP enabled). If a step-by-step example is

 

needed to fully configure the RUI/Gateway refer to step one and download the appropriate

 

user manual.

 

 

 

 

5.

To implement the network shown in step two the following settings will need to be entered:

 

 

 

 

 

 

 

 

 

 

Gateway

 

Enable

Modbus®

 

 

 

 

Instance

 

Gateway

Offset

 

 

 

 

 

Instance

 

 

 

 

 

 

 

 

 

 

 

GTW = 1

 

Du;En = Yes

M;oF = 0

 

 

 

 

GTW = 2

 

Du;En = Yes

M;oF = 5000

 

 

 

 

GTW = 3

 

Du;En = Yes

M;oF = * 10000

 

 

 

 

GTW = 4

 

Du;En = Yes

M;oF = * 15000

 

 

 

Further explanation of these prompts and their associated enumerated values will follow.

 

* The RUI allows for a maximum entry of 9999 due to the limitations of the 7 segment display. To enter

 

 

an offset > 9999 EZ-ZONE®configurator software must be used.

 

6.

After completing the configuration as shown above as well as your Com 1 settings for the

 

Standard Bus side this will complete the RUI/Gateway configuration.

 

7.

Note that KEPServerEX is one of many software packages on the market today that include

 

the Modbus® TCP driver; this procedure is for KEPServerEX.

 

8.

The following screen shots capture a step-by-step procedure to successfully establish

 

Communications between the computer (PC) running KEPServerEX and the EZ-ZONE®

 

RUI/Gateway (Com instance 2) over Modbus® TCP. Once communications are established

 

over Com instance 2 we will then look further at the KEPServerEX configuration that will

 

enable communications through the RUI/Gateway to Com instance 1 and the EZ-ZONE®PM

 

controls (1 - 4) over Standard Bus; thereby establishing a live and active communications link

 

between dissimilar networks.

 

Watlow

 

 

 

 

1241 Bundy Blvd

 

 

 

 

Winona, MN 55987

 

 

 

 

Telephone: 507-494-5656

 

 

 

© 2008 Watlow Electric Mfg Co

2

FM 4/08

Page 2
Image 2
Watlow Electric user manual RUI/Gateway & Modbus TCP, Configuration & Programming Example, Using KEPServerEX