Watlow Electric user manual RUI/Gateway & Modbus TCP Configuration & Programming Example

Models: RUI/Gateway

1 20
Download 20 pages 7.64 Kb
Page 19
Image 19
39.The address shown above represents pointer 12 as shown in the EZ-ZONE®PM Communications user manual under the sub-heading of “User Programmable Memory Blocks”.

RUI/Gateway & Modbus® TCP

Configuration & Programming Example

Using KEPServerEX 4.0

39.The address shown above represents pointer 12 as shown in the EZ-ZONE®PM Communications user manual under the sub-heading of “User Programmable Memory Blocks”.

Again, focus on the address below. This particular address represents the Assembly Working Address for pointer 12.

40.Now that the tags are created execute the OPC quick client as illustrated in step 33. Once running, click on the tag created to modify the assembly. In this case, “New Assembly - Pointer 12”. Based on the “Description” field in the screen shot in step 38 and 39 pointer 12 will become the Idle Set Point of PM1 once changed. The value to be written below reflects this.

Watlow

 

 

1241 Bundy Blvd

 

 

Winona, MN 55987

 

 

Telephone: 507-494-5656

 

 

© 2008 Watlow Electric Mfg Co

19

FM 4/08

Page 19
Image 19
Watlow Electric user manual RUI/Gateway & Modbus TCP Configuration & Programming Example, Using KEPServerEX